background image

R7HL-DAC15E

EM-7812-AY  Rev.1  P. 2 / 5

COMPONENT IDENTIFICATION

X10

X1

STATION ADD.

1

2

3

4

5

6

7

8

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

4

5

6

7

1

2

3

TERM

ON

OFF

RUN

PWR

ON

0

1

2

3

4

5

6

7

0

1

2

3

4

5

6

■ 

FRONT VIEW

■ 

SIDE VIEW

012

34

56

789AB

C

D

EF

012

34

56

789AB

C

D

EF

Terminating Resistor SW

Status Indicator LED

Station Address Setting Rotary SW

Operating Mode Setting DIP SW (SW1)

Discrete I/O

Status Indicator LED

I/O Terminals

Network, Power Supply

Terminals

INPUT

OUTPUT

 

STATUS INDICATOR LED

ID

COLOR

FUNCTION

PWR

Green

Turns on when the internal 5V is sup-
plied normally.

RUN

Green

Turns on when the refresh data is re-
ceived normally. 

 

DISCRETE I/O STATUS INDICATOR LED

LED indicators shows the signal status.

ON   : LED ON (red)
OFF : LED OFF

 

STATION ADDRESS

The left switch determines the sixteenths place digit, while
the right switch does the ones place digit of the address.
(Range: 01H to 3FH)

Station Address Setting (x1)

Station  Address Setting (x16)

012

34

56

789AB

C

D

EF

012

34

56

789AB

C

D

EF

 

OPERATING MODE

(*) Factory setting

• Output at the loss of communication (SW1-7)

SW1-7

OUTPUT AT THE LOSS OF COMMUNICATION

OFF

Hold the output (*)
(maintains the last data received normally) 

ON

Reset the output (turned off) 

• Transfer rate (SW1-8)

SW1-8

TRANSFER RATE

OFF

12 Mbps (*)

ON

6 Mbps

Note: Be sure to set unused SW1-1 through 1-6 to OFF.

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and
OFF to invalidate.  (Factory setting OFF)

 

NETWORK, POWER SUPPLY TERMINAL ASSIGNMENT

• Full-duplex communication

4

RXD+

5

6

7

1

2

3

RXD– +24V 0V

TXD+ TXD– FG

NO.

ID

FUNCTION, NOTES

1

TXD+

Network (slave, transm)

2

TXD–

Network (slave, transmission –)

3

FG

FG

4

RXD+

Network (master, transm)

5

RXD–

Network (master, transmission –)

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

• Half-duplex communication

4

TR

+

5

6

7

1

2

3

TR

– +

24V

0V

NC

NC

FG

NO.

ID

FUNCTION, NOTES

1

NC

No connection

2

NC

No connection

3

FG

FG

4

TR+

Network

5

TR–

Network

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Reviews: