R7G4HEIP-6-DC16A
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8004-B P. 2 / 6
FRONT VIEW
4
5
6
7
1
2
3
10 11 12 13
2
3
4
1
15 16 17 18
7
8
9
6
14
5
PWR
SA1
×10
SA2
×1
LNK2
NS
LNK1
MS
LNK1
LNK2
CNFG.
Status Indicator LED
RJ-45 Modular Jack
IP Address Setting
Rotary SW
PC Configurator Jack
Output Terminals
Power Supply Terminals
Discrete Output Status Indicator LED
■
STATUS INDICATOR LED
ID
STATUS
COLOR FUNCTION
PWR
ON
Green
The internal power is supplied
normally.
MS
ON
Green
Operating in a normal condition
Blinking
Standby (needs commissioning)
ON
Red
Critical failure
Blinking
Minor failure
OFF
–
No power supplied
NS
ON
Green
Link on-line and connections in
the established state
Blinking
Link on-line but no connections
in the established state
ON
Red
Critical failure
Blinking
Minor failure
OFF
–
No power supplied
LNK1
ON
Green
LNK1 is established
LNK2
ON
Green
LNK2 is established
■
IP ADDRESS
Set host address (2-digit hexadecimal number) in IP ad-
dress, with rotary switches SA1 for the first digit and SA2
for the second digit, or when using network address and
Subnet mask with modification, set 00H with the rotary
switches and then set the parameters with PC configurator
software (model: R7CFG). (Range: 00H – FFH)
(Factory setting: 01H)
IP Address Host Address MSD (x1)
IP Address Host Address LSD (x10)
012
34
56
789
AB
C
DE
F
012
34
56
789
AB
C
DE
F
■
DISCRETE OUTPUT STATUS INDICATOR LED
Discrete output module displays the status of each output
with an LED (green).
Contact ON : LED ON
Contact OFF : LED OFF
■
PC CONFIGURATOR JACK
The PC Configurator is used to set the following parameters
for each channel.
• IP address setting
- IP address: 192.168.0.1
- Subnet mask: 255.255.255.0
- Default gateway: 192.168.0.1
• Communication Cutoff Output Settings
Output clear (Output OFF)
Output hold (Previous normal reception data hold) (*)
For more information about the programming using the
R7CFG, please refer to the R7CFG Users Manual.
(*) Factory setting
4
NC
5
6
7
1
2
3
NC
+
24V 0V
NC
NC
FE
1.
NC
2.
NC
3.
FE
4.
NC
5.
NC
6.
+24V
7.
0V
-
-
Functional earth
-
-
Power supply (24V DC)
Power supply (0V)
■
POWER SUPPLY TERMINAL ASSIGNMENT
■
OUTPUT TERMINAL ASSIGNMENTS
14
5
6
Y7
Y6
Y8
15
Y9
16
17
18
7
8
9
Y11 Y13 Y15
Y10 Y12
10
1
2
V+
V−
Y0
11
Y1
12
13
3
4
Y3
Y5
Y2
Y4
Y14
NO.
ID
FUNCTION
NO.
ID
FUNCTION
1
V–
0V (Out. Common)
10
V+ 24V DC
2
Y0
Output 0
11
Y1
Output 1
3
Y2
Output 2
12
Y3
Output 3
4
Y4
Output 4
13
Y5
Output 5
5
Y6
Output 6
14
Y7
Output 7
6
Y8
Output 8
15
Y9
Output 9
7
Y10 Output 10
16
Y11 Output 11
8
Y12 Output 12
17
Y13 Output 13
9
Y14 Output 14
18
Y15 Output 15