R7F4HML3-D-DAC32B
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax:
+81(6)6659-8510 E-mail: [email protected]
EM-8002-B Rev.2 P. 1 / 12
INSTRUCTION MANUAL
NPN
/
PNP DISCRETE INPUT & PNP TRANSISTOR OUTPUT MODULE, 16 points each
(MECHATROLINK- III use)
MODEL
R7F4HML3-D-DAC32B
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■
PACKAGE INCLUDES:
Discrete input module .........................................................(1)
DIN rail mounter slider ......................................................(2)
■
MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■
CONFORMITY WITH EU DIRECTIVES
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrat-
ed in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■
POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 100mA
■
GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and I/O signal for safety.
• Before you remove the terminal block MIL connector or
mount it, turn off the power supply and I/O signal for
safety.
■
ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to 55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• With vertical mounting, for heat dissipation leave at least
10 mm (.39 in.) at the both side of the unit.
■
WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■
AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
All manuals and user guides at all-guides.com
all-guides.com