R7E-PA8

EM-7807-AJ  P. 7 / 8

MODBUS FUNCTION CODES & SUPPORTED CODES

 

DATA AND CONTROL FUNCTIONS

CODE

NAME

01

Read Coil

Status Digital output from the slave (read/write)

02

Read Input Status

Status of digital inputs to the slave (read only)

03

Read Holding Registers

General purpose register within the slave (read/write)

04

Read Input Registers

Collected data from the field by the slave (read only)

05

Force Single Coil

Digital output from the slave (read/write)

06

Preset Single Register

General purpose register within the slave (read/write)

08

Diagnostics

11

Fetch Comm. Event Counter

Fetch a status word and an event counter

12

Fetch Comm. Event Log

A status word, an event counter, a message count and a field of event bytes

15

Force Multiple Coils

Digital output from the slave (read/write)

16

Preset Multiple Registers

General purpose register within the slave (read/write)

17

Report Slave ID

Slave type/‘RUN’ status

 

EXCEPTION CODES

CODE

NAME

01

Illegal Function

Function code is not allowable for the slave

02

Illegal Data Address

Address is not available within the slave

03

Illegal Data Value

Data is not valid for the function

 

DIAGNOSTIC SUBFUNCTIONS

CODE

NAME

00

Return Query Data

Loop back test

MODBUS I/O ASSIGNMENT

ADDRESS

DATA TYPE

DATA

Coil (0X)

1 – 16

Digital Output (discrete output of the basic module)

17 – 32

Digital Output (discrete output of the extension module)

Inputs (1X)

1 – 16

Digital Input (discrete input of the basic module)

17 – 32

Digital Input (discrete input of the extension module)

33 – 48

Reserved (unused)

49 – 64

Module Status

65 – 80

Reserved (unused)

Input Registers (3X)

1 – 4

I

Analog Input

5 – 16

----

Reserved (unused)

17 – 24

F

Analog Input

25 – 48

----

Reserved (unused)

Holding Registers (4X)

1 – 2

I

Analog Output

3 – 16

----

Reserved (unused)

17 – 20

F

Analog Output

21 – 48

----

Reserved (unused)

I: Integer, -1500 – +11500 (-15 – +115%)
F: Floating
Note: DO NOT access addresses other than mentioned above.  Such access may cause problems such as inadequate operation.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7E-PA8-R

Page 1: ...y and input signal for safety DO NOT set the switches on the module while the power is supplied The switches are used only for maintenance without the power ENVIRONMENT Indoor use When heavy dust or m...

Page 2: ...signal status ON LED ON OFF LED OFF OPERATING MODE Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF OFF No extension ON OFF Discrete input 8 or 16 points OFF ON Discrete output 8 or 16 points Factory set...

Page 3: ...76 7 sec 180 0 sec CHANNEL INDIVIDUAL SETTING PARAMETER SETTING RANGE DEFAULT SETTING Max 1 000 4 294 967 295 9 999 999 Carry 0 1 0 Preset 0 4 294 967 295 EXTENSION MODULE SETTING PARAMETER SETTING RA...

Page 4: ...V PI0 C0 18 PI7 9 C7 1 10 2 11 V V PI0 C0 1 5 10 2 6 4 7 13 8 9 14 12 15 11 16 17 18 V V C1 C2 C3 C4 C5 C6 C7 PI0 PI7 PI1 PI2 PI3 PI4 PI5 PI6 C0 3 PNP connection NPN connection Input Connection Examp...

Page 5: ...4 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statistics for Packets Sent 4 Received 4 Lost 0 0 loss Replies in case of normal connection are as shown above If the c...

Page 6: ...write data upper 21 CH 2 Return value read data upper 22 CH 2 Return value write data lower 22 CH 2 Return value read data lower 23 CH 3 Return value write data upper 23 CH 3 Return value read data up...

Page 7: ...pe RUN status EXCEPTION CODES CODE NAME 01 Illegal Function Function code is not allowable for the slave 02 Illegal Data Address Address is not available within the slave 03 Illegal Data Value Data is...

Page 8: ...MINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable wire size 0 25 to 1 65 mm2 AWG 22 to 16 Re...

Reviews: