PC CONFIGURATOR

The following parameter items can be set with using PC Configurator Software (model: R7CON).
Refer to the users manual for the R7CON for detailed operation of the software program.

 

INTERFACE SETTING 

PARAMETER

SETTING RANGE

DEFAULT SETTING

Communication Timeout

0.0 – 3276.7 (sec.)

3.0 (sec.) 

 

ETHERNET SETTING 

PARAMETER

SETTING RANGE

DEFAULT SETTING

IP Address

0.0.0.0 – 255.255.255.255

192.168.0.1

Subnet Mask

0.0.0.0 – 255.255.255.255

255.255.255.0

Linger

0.0 – 3276.7 (sec.)

180.0 (sec.)

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

SETTING RANGE

DEFAULT SETTING

Zero scale

-32000 to +32000

0

Full scale

-32000 to +32000

10000

Zero base

0 to 10000

0

Ful base

0 to 10000

10000

 

EXTENSION MODULE SETTING

PARAMETER

SETTING RANGE

DEFAULT SETTING

Output Hold/Clear

Output Hold
Output Clear

Output Hold

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

30 (1.18)

65 (2.56)

[5 (.20)]

3

(.12)

5.5 (.22)

DIN RAIL

35mm wide

54 (2.13)

17 (.66)

50 (1.97)

18.5 (.73)

115 (4.53)

RJ-45 CONNECTOR

7–M3 SCREW

TERMINALS

for POWER

18–M3 SCREW 

TERMINALS

for INPUT

6 (.24)

6 (.24)