R7D-TS4

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7802-B  Rev.10  P. 3 / 10

PC CONFIGURATOR

The following parameter items can be set with using PC Configurator Software (model: R7CON).
Refer to the users manual for the R7CON for detailed operation of the software program.

 

INTERFACE SETTING 

PARAMETER

SETTING RANGE

DEFAULT SETTING

Communication Timeout

0.0 – 3276.7 (sec.)

1.0 (sec.) 

Status Data

ON: Disable
OFF: Enable

OFF: Enable

Serial ID

English one-byte characters within 8 characters

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

SETTING RANGE

DEFAULT SETTING

TC Type

K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)


C (WRe 5-26)



P (Platinel II)
(PR)

K (CA)

Temp Unit

C, F, K

C

Zero scale

-32000 to +32000

0

Full scale

-32000 to +32000

10000

Bias

-320.00 to +320.00

0.00

Gain

-3.2000 to +3.2000

1.0000

Zero temp

Depends on sensor type

0.00 (degC)

Full temp

Depends on sensor type

0.00 (degC)

 

EXTENSION MODULE SETTING

PARAMETER

SETTING RANGE

DEFAULT SETTING

Output Hold/Clear

Output Hold
Output Clear

Output Hold

Summary of Contents for R7D-TS4

Page 1: ...ipment is suitable for use in Installation Catego ry II and in a Pollution Degree 2 environment Altitude up to 2000 meters This equipment must be mounted inside a suitable fire enclosure This equipmen...

Page 2: ...00 kbps 3 thr 9 Auto tracking The R7D communicates in the baud rate setting detected at the startup with the switch set to the positions 0 125 kbps 1 250 kbps or 2 500 kbps For the settings 3 through...

Page 3: ...Timeout 0 0 3276 7 sec 1 0 sec Status Data ON Disable OFF Enable OFF Enable Serial ID English one byte characters within 8 characters CHANNEL INDIVIDUAL SETTING PARAMETER SETTING RANGE DEFAULT SETTING...

Page 4: ...15 4 53 18 M3 SCREW TERMINALS for INPUT 6 24 TERMINAL BLOCK for DeviceNet POWER 7 28 30 1 18 5 20 DIN RAIL 35mm wide 54 2 13 17 66 CONNECTION DIAGRAM 10 IN0 11 IN0 1 CJ0 2 CJ0 IN1 IN1 CJ1 CJ1 IN2 IN2...

Page 5: ...e R7D EA16 with Status Analog Input Module CH0 CH1 CH2 CH3 Begin 0 1 2 3 Output Data Analog Input Module Status CH0 CH1 CH2 Begin 0 Begin 0 1 2 CH3 3 4 Output Data Input Data None Example 1 Analog Inp...

Page 6: ...PUT DATA 2 R7D to Master Master to R7D R7D TS4 4 0 EXTENSION MODULE Transmitted data word for the extension module is added MODEL OUTPUT DATA 1 INPUT DATA 2 R7D to Master Master to R7D R7D EAx 1 0 R7D...

Page 7: ...ing the R7D Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out...

Page 8: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the co...

Page 9: ...ement Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions f...

Page 10: ...tween cables and noise sources Grounding in pig tail form is not effective Points of cautions applicable when wiring the R7D Series To external apparatus Keep the cable as short as possible To externa...