R7D-TS4

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7802-B  Rev.10  P. 2 / 10

COMPONENT IDENTIFICATION

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

MS

X10

X1

NODE ADD.

B.RATE

CNFG.

1

2

3

4

5

6

7

8

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

NS

2 3 4

1

5

(A)  Status Indicator LED
(B)  Node Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  DeviceNet, Power Supply Terminals
(G)  Input Terminals

(A)

(F)

(G)

(B)

(C)

(D)

(E)

 

STATUS INDICATOR LED

ID

STATE

TO INDICATE

MS

Green

Operating in a normal condition

Blinking Green Standby (needs commissioning)

Red

Critical failure

Blinking Red

Minor failure

OFF

No power supplied

NS

Green

Link on-line and connections in the 
established state

Blinking Green Link on-line but no connections in 

the established state

Red

Critical link failure

Blinking Red

Minor link failure

OFF

No power supplied

 

NODE ADDRESS

Node Address is selected between 1 and 63 in decimal.  The 
left switch determines the tenth place digit, while the right 
switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Factory setting : 00

Node Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0 : 125 kbps (factory setting)
1 : 250 kbps
2 : 500 kbps
3 thr. 9 : Auto-tracking

The R7D communicates in the baud rate setting detected at 
the startup with the switch set to the positions 0 (125 kbps), 
1 (250 kbps) or 2 (500 kbps).
For the settings 3 through 9, it analyzes the PLC’ s network 
to determine the baud rate on the network.

 

OPERATING MODE

(*) Factory setting

• Extension: SW1-1, 1-2

SW1-1

SW1-2 EXTENSION

OFF

OFF

No extension (*)

ON

OFF

Discrete input, 8 or 16 points

OFF

ON

Discrete output, 8 or 16 points

• 

Conversion Rate: SW1-3      • Burnout: SW1-4

SW1-3

CONVERSION RATE

SW1-4

BURNOUT

OFF

250 msec. (*)

OFF

Upscale (*)

ON

500 msec.

ON

Downscale

• Thermocouple Type: SW1-5, 1-6, 1-7, 1-8

SW1-5

SW1-6

SW1-7

SW1-8 THERMOCOUPLE TYPE

OFF

OFF

OFF

OFF

K (CA) (*)

ON

OFF

OFF

OFF

E (CRC)

OFF

ON

OFF

OFF

J (IC)

ON

ON

OFF

OFF

T (CC)

OFF

OFF

ON

OFF

B (RH)

ON

OFF

ON

OFF

R

OFF

ON

ON

OFF

S

ON

ON

ON

OFF

C (WRe 5-26)

OFF

OFF

OFF

ON

N

ON

OFF

OFF

ON

U

OFF

ON

OFF

ON

L

ON

ON

OFF

ON

P (Platinel II)

OFF

OFF

ON

ON

(PR)

ON

ON

ON

ON

PC Configurator setting

 

DeviceNet TERMINAL ASSIGNMENT

2

3

4

1

5

NO.

ID

FUNCTION, NOTES

1

V+

Network power

2

CAN_H

Network data High

3

Drain

Shield

4

CAN_L

Network data Low

5

V–

Network power supply –

 

INPUT TERMINAL ASSIGNMENT

10

+IN0

11

–IN0

12

+IN1

1

+CJ0

2

–CJ0

3

+CJ1

13

–IN1

4

–CJ1

14

NC

5

NC

15

+IN2

6

+CJ2

16

–IN2

7

–CJ2

17

+IN3

8

+CJ3

9

–CJ3

18

–IN3

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

+CJ0 CJC 0

10 +IN0 T/C + 0

2

–CJ0 CJC 0

11 –IN0 T/C – 0

3

+CJ1 CJC 1

12 +IN1 T/C + 1

4

–CJ1 CJC 1

13 –IN1 T/C – 1

5

NC

No connection

14

NC

No connection

6

+CJ2 CJC 2

15 +IN2 T/C + 2

7

–CJ2 CJC 2

16 –IN2 T/C – 2

8

+CJ3 CJC 3

17 +IN3 T/C + 3

9

–CJ3 CJC 3

18 –IN3 T/C – 3

 

EXTENSION MODULE

Combinations with all extension modules are selectable.

Summary of Contents for R7D-TS4

Page 1: ...ipment is suitable for use in Installation Catego ry II and in a Pollution Degree 2 environment Altitude up to 2000 meters This equipment must be mounted inside a suitable fire enclosure This equipmen...

Page 2: ...00 kbps 3 thr 9 Auto tracking The R7D communicates in the baud rate setting detected at the startup with the switch set to the positions 0 125 kbps 1 250 kbps or 2 500 kbps For the settings 3 through...

Page 3: ...Timeout 0 0 3276 7 sec 1 0 sec Status Data ON Disable OFF Enable OFF Enable Serial ID English one byte characters within 8 characters CHANNEL INDIVIDUAL SETTING PARAMETER SETTING RANGE DEFAULT SETTING...

Page 4: ...15 4 53 18 M3 SCREW TERMINALS for INPUT 6 24 TERMINAL BLOCK for DeviceNet POWER 7 28 30 1 18 5 20 DIN RAIL 35mm wide 54 2 13 17 66 CONNECTION DIAGRAM 10 IN0 11 IN0 1 CJ0 2 CJ0 IN1 IN1 CJ1 CJ1 IN2 IN2...

Page 5: ...e R7D EA16 with Status Analog Input Module CH0 CH1 CH2 CH3 Begin 0 1 2 3 Output Data Analog Input Module Status CH0 CH1 CH2 Begin 0 Begin 0 1 2 CH3 3 4 Output Data Input Data None Example 1 Analog Inp...

Page 6: ...PUT DATA 2 R7D to Master Master to R7D R7D TS4 4 0 EXTENSION MODULE Transmitted data word for the extension module is added MODEL OUTPUT DATA 1 INPUT DATA 2 R7D to Master Master to R7D R7D EAx 1 0 R7D...

Page 7: ...ing the R7D Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out...

Page 8: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the co...

Page 9: ...ement Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions f...

Page 10: ...tween cables and noise sources Grounding in pig tail form is not effective Points of cautions applicable when wiring the R7D Series To external apparatus Keep the cable as short as possible To externa...

Reviews: