EM-7802-G  Rev.5  P. 1 / 10

INSTRUCTION MANUAL

NPN TRANSISTOR OUTPUT MODULE, 16 points

(DeviceNet) 

MODEL

R7D-DC16A

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Discrete output module.......................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.

 

EDS FILE

EDS files are downloadable at M-System’s web site: https://
www.m-system.co.jp

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside the instrument

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system.  The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and output signal for safety.

• Before you remove the terminal block or mount it, make

sure to turn off the power supply and output signal for
safety.

• DO NOT set the switches on the module while the power

is supplied.  The switches are used only for maintenance
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the

air, install the unit inside proper housing with sufficient
ventilation.

• Do not install the unit where it is subjected to continuous

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C

(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive

cable, high frequency line, etc.).

• Do not bind these cables together with those in which

noises are present.  Do not install them in the same duct.

• Be sure to close the terminal cover for safety.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7D-DC16A

Page 1: ...al protective measures to ensure the CE conform ity GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and output signal for safety Before you remove the terminal blo...

Page 2: ...selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 125 kbps factory setting 1 250 kbps 2 500 kbps 3 thr 9 Auto tracking The R7D communicates in the baud rate setting detected at...

Page 3: ...F Enable Serial ID English one byte characters within 8 characters EXTENSION MODULE SETTING PARAMETER SETTING RANGE DEFAULT SETTING Output Hold Clear Output Hold Output Clear Output Hold TERMINAL CONN...

Page 4: ...t Connection Example 10 1 2 Y0 0V 24V 3 Y1 18 YF CAN_L V Drain CAN_H V EXTENSION CONNECTOR DATA ALLOCATION Begin address is determined by the R7D s node address and the master setting Status Begin 0 B...

Page 5: ...ISCRETE I O STATUS Bit 0 to 7 Discrete output module shows 0 at the same address Bit 8 to 10 Shows the power supply status 0 15 Remains 0 Remains 0 Remains 0 Unused Remains 0 Remains 0 Remains 0 Remai...

Page 6: ...r to STATUS in I O DATA DESCRIPTIONS STATUS OUTPUT DATA 1 INPUT DATA 2 R7D to Master Master to R7D Enabled 1 0 Disabled 0 0 1 Output Data means those sent to the master 2 Input Data means those receiv...

Page 7: ...a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7D modul...

Page 8: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Page 9: ...f cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impac...

Page 10: ...applicable when wiring the R7D Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it...