• Prevent noise leakage by wrapping cables using shield covers, shield tubes and flexible conduits etc. if noise leaks through 

the cable outlet.

• Use an electromagnetic shield gasket and block up the gap between the control panel cabinet and its cover, if noise leaks 

through it.

• Connecting the internal panel plate and the cover of the control panel to the main cabinet using an earth strap may be 

effective to strengthen the grounding.

• Electromagnetically shielded control panel cabinet is effective for shielding.

Use (e.g.) a shield cover 
when noise leaks through 
the opening.

To external apparatus

Keep the opening

for cabling as small as

possible.

Install an electromagnetically
shielded gasket when 
noise leaks through 
the opening.

Shielding is strengthened 
by using an electro-
magnetically shielded 
control panel.

By connecting the
internal panel plate 
and the panel cover with 
an earth strap, grounding 
may be strengthened and
EMC may be improved.

Ground the control panel 

at low impedance using 

 (e.g.) braided wires.

Keep the opening for 

ventilation as small as

posible.

Attach an electro-
magnetically shielded
filter when noise leaks 
through the opening.

Install the R7C Series inside

a control panel.

Attachment part of earth

clamp should be fixed with 

screw in conduction with the

internal panel plate.

• Points of cautions applicable when installing the R7C Series

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7C-EC8A/UL

Page 1: ...d by a Class 2 power sup ply CONFORMITY WITH EU DIRECTIVES The equipment must be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole syst...

Page 2: ... 0 7 Y1 Output 1 3 Y2 Output 2 8 Y3 Output 3 4 Y4 Output 4 9 Y5 Output 5 5 Y6 Output 6 10 Y7 Output 7 CONNECTING THE EXTENSION MODULE 1 Remove the extension connector cover located at the side of the basic module 2 Connect the extension module 3 Mount the combined module on a DIN rail TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 11 5 45 7 8 6 9 10 ...

Page 3: ...ol panel This is effective not only to ensure general safety but also to contain noise emissions by the R7C inside the control panel We conduct a series of testing to see that the product conforms to EMC Direc tive while it is installed in the control panel Warning and cautions when installing R7C are stated below Use control panels with an internal panel plate both made of metal when installing t...

Page 4: ...ep the opening for cabling as small as possible Install an electromagnetically shielded gasket when noise leaks through the opening Shielding is strengthened by using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g b...

Page 5: ...tions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the control panel or close to the I O terminal or connector whichever is more effective Also the im...

Page 6: ...tus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect with apparatuses outside the control panel via CC Link ground the cable shield using an earth clamp Keep the wires away from each other at both ends of the filter 056 222 38 18 mailbox sentronic ...

Reviews: