EM-7781-BI Rev.3 P. 4 / 4
1) Insert a minus screwdriver into the wire entry opening,
between the clamp and the housing, until its tip hits the
bottom where it is firmly held.
Tension Clamp
Screwdriver
2) Insert a wire. Push the screwdriver toward the direction
indicated with the arrow in the figure below to widen the
opening if necessary.
Wire Entry
Wire
3) Confirm that the wire tip hits the bottom and pull out the
screwdriver in holding it in position.
Confirm that the wire’s insulation tube is not caught in
the clamp.
PC CONFIGURATOR
With configurator software, settings shown below are avail-
able.
Refer to the software manual of R6CON for detailed opera-
tion.
■
CHANNEL INDIVIDUAL SETTING
PARAMETER
AVAILABLE RANGE
DEFAULT SETTING
Sensor type
K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)
R
S
C (WRe 5-26)
N
U
L
P (Platinel II)
(PR)
K (CA)
Lower range value
Depends on sensor type 0.00 (degC)
Upper range value
Depends on sensor type 0.00 (degC)
Fine zero adjustment -320.00 to +320.00 (%)
0.00 (%)
Fine gain adjustment -3.2000 to +3.2000
1.0000
Scaled range Zero
-32000 to +32000
0
Scaled range Span
-32000 to +32000
10000
Burnout
Upscale, Downscale
Upscale
■
CHANNEL BATCH SETTING
PARAMETER
AVAILABLE RANGE
DEFAULT SETTING
Loss of internal bus
communication detec-
tion time
0.0 – 99.9 (sec.)
1.0 (sec.)
Conversion rate
250, 500 (msec.)
500 (msec.)
Temperature unit
degC, degF, K
degC
CJC
ON, OFF
ON
Limit
-15 to +115%
Scaled range Zero / Span
-15 to +115%