INSTRUCTION MANUAL
POWER SUPPLY MODULE
MODEL
R6-PSM
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■
PACKAGE INCLUDES:
Power supply module ..........................................................(1)
■
MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■
CONFORMITY WITH EU DIRECTIVES
•
This equipment is suitable for Installation Category II
(transient voltage 2500V), Measurement Category II
(RUN contact output, transient voltage 2500V) and Polu-
tion Degree 2.
•
Reinforced insulation (internal power or RUN contact
output to power input to FG: 300V) and basic insulation
(internal power to RUN contact output: 300V) are main-
tained. Prior to installation, check that the insulation
class of this unit satisfies the system requirements.
•
The equipment must be mounted inside a panel.
•
Altitude up to 2000 meters.
•
The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
•
The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
•
Install lightning surge protectors for those wires connect-
ed to remote locations.
■
POWER INPUT RATING & OPERATIONAL RANGE
•
Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 90 – 264V, 47 – 66 Hz,
approx. 35VA
■
GENERAL PRECAUTIONS
•
Before you remove the unit from its base or mount it, turn
off the power supply for safety.
■
ENVIRONMENT
•
Indoor use.
•
When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
•
Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•
Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
•
Be sure that the ventilation slits are not covered with ca-
bles, etc.
•
Keep space of at less 1 cm (0.4 inches) on the left side of
the power supply.
■
WIRING
•
Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•
Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■
AND ....
•
The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
4 5 6
1 2 3
POWER
Power LED
Connector Euro type
terminal block
■
INDICATOR LED
ID
COLOR
FUNCTION
Power
OFF
Power supply off
Green ON
Power supply on
Abnormal communication
Orange ON Power supply on
Normal communication status
INSTALLATION
Use the Installation Base (model: R6x-BS8B).
In order to remove this module from a base, push the lock-
ing clamp with a minus screwdriver.