INSTRUCTION MANUAL

POWER SUPPLY MODULE

MODEL

R6-PSM

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Power supply module ..........................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• 

This equipment is suitable for Installation Category II 
(transient voltage 2500V), Measurement Category II 
(RUN contact output, transient voltage 2500V) and Polu-
tion Degree 2. 

• 

Reinforced insulation (internal power or RUN contact 
output to power input to FG: 300V) and basic insulation 
(internal power to RUN contact output: 300V) are main-
tained.  Prior to installation, check that the insulation 
class of this unit satisfies the system requirements.

• 

The equipment must be mounted inside a panel.

• 

Altitude up to 2000 meters.

• 

The equipment must be installed such that appropriate 
clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• 

The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

• 

Install lightning surge protectors for those wires connect-
ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

• 

Locate the power input rating marked on the product and 
confirm its operational range as indicated below:

    100 – 240V AC rating:  90 – 264V, 47 – 66 Hz,  

 

approx. 35VA

 

GENERAL PRECAUTIONS

• 

Before you remove the unit from its base or mount it, turn 
off the power supply for safety.

 

ENVIRONMENT

• 

Indoor use.

• 

When heavy dust or metal particles are present in the 
air, install the unit inside proper housing with sufficient 
ventilation.

• 

Do not install the unit where it is subjected to continuous 
vibration.  Do not subject the unit to physical impact.

• 

Environmental temperature must be within -10 to +55°C 
(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

• 

Be sure that the ventilation slits are not covered with ca-
bles, etc.

• 

Keep space of at less 1 cm (0.4 inches) on the left side of 
the power supply.

 

WIRING

• 

Do not install cables close to noise sources (relay drive 
cable, high frequency line, etc.).

• 

Do not bind these cables together with those in which 
noises are present.  Do not install them in the same duct.

 

AND ....

• 

The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

COMPONENT IDENTIFICATION

4 5 6

1 2 3

POWER

Power LED

Connector Euro type

 terminal block

 

INDICATOR LED

ID

COLOR

FUNCTION

Power

OFF

Power supply off

Green ON

Power supply on
Abnormal communication

Orange ON Power supply on

Normal communication status

INSTALLATION

Use the Installation Base (model: R6x-BS8B).
In order to remove this module from a base, push the lock-
ing clamp with a minus screwdriver.