COMPONENT IDENTIFICATION

RUN

4

3

2

1

6

5

RUN LED

ON

1 2 3 4 5 6 7 8

RTD

Burnout

Temp. Unit

Function

■ 

SIDE VIEW

 FRONT VIEW

 

STATUS INDICATOR LED

RUN indicator

:  Bi-color (red/green) LED;  

 

Red when the bus A operates normally; 

 

Green when the bus B operates normally; 

 

Amber when both buses operate normally.

 

SIDE DIP SW

(*) Factory setting

• RTD Type: SW1, 2, 3, 4

SW

RTD

1

2

3

4

ON

OFF

ON

OFF

Cu 10 @ 25°C

OFF

OFF

OFF

OFF

Cu 50

OFF

OFF

OFF

ON

JPt 100 (JIS ’89)

ON

OFF

OFF

OFF

Pt 100 (JIS ’89)

OFF

ON

OFF

OFF

Pt 100 (JIS ’97, IEC) (*)

OFF

ON

ON

OFF

Pt 1000

ON

ON

OFF

OFF

Pt 50 Ω (JIS ’81)

OFF

OFF

ON

OFF

Ni 100

ON

ON

ON

OFF

Ni 508.4 Ω

• Temperature Unit: SW5, 6

SW

TEMP. UNIT

5

6

OFF

OFF

°C (*)

ON

OFF

°F

OFF

ON

K (Absolute Temp)

• Burnout: SW7, 8

SW

BURNOUT

7

8

INPUT 1

INPUT 2

OFF

OFF

Downscale

ON

ON

Upscale (*)

PC CONFIGURATOR

With configurator software, settings shown below are available.
Refer to the software manual of R5CON for detailed operation.

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Zero Scale

-32000 to +32000

0

Full Scale

-32000 to +32000

10000

Bias [Zero Adj.]

-320.00 to +320.00

0.00

Gain [Span Adj.]

-32000 to +32000

1.0000

Zero Base

Depends on sensor type

0.00

Full Base

Depends on sensor type

0.00

 

CHANNEL BATCH SETTING

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Limit

No check mark:  Limits to the scaling values equivalent to -15 % to 

+115 %.

Check-marked: Limits within Zero Scale to Full Scale.

No check mark