background image

R3Y-SV8N

P. 2 / 3

EM-8954 Rev.1

COMPONENT IDENTIFICATION

Conversion Rate

: SW3

SW

CONVERSION RATE

100 ms (

*

)

50 ms

20 ms

10 ms

SW3-1

OFF

ON

OFF

ON

SW3-2

OFF

OFF

ON

ON

(*) Factory setting

SIDE DIP SW

Input Range

: SW1, SW2 (selectable per 4 channels)

INPUT 1 through INPUT 4 (SW1)

INPUT 5 through INPUT 8 (SW2)

RANGE

1

2

3

4

OFF

OFF

OFF

OFF

-10 – +10V (*)

ON

OFF

OFF

OFF

-5 – +5V

ON

ON

OFF

OFF

0 – 10V

OFF

OFF

ON

OFF

0 – 5V

ON

OFF

ON

OFF

1 – 5V

RUN LED

ERR LED

■ 

FRONT VIEW

■ 

SIDE VIEW

• Pin Assignment

B

20

A

20

B

1

A

1

Input Connector

Range

Input 1-4 (SW1)
  or
Input 5-8 (SW2)

ON

8
7
6
5
4
3
2
1

SW1

SW2

ON

8
7
6
5
4
3
2
1

Conv.
Rate

SW3

ON

4
3
2
1

STATUS INDICATOR LED

RUN indicator

: Bi-color (red/green) LED;

Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

ERR indicator

: Bi-color (red/green) LED;

Red with the input circuit abnormality (AD
converter response failure);
Green in normal operating conditions.