![background image](http://html1.mh-extra.com/html/m-system/r3y-sv8n/r3y-sv8n_instruction-manual_3168542002.webp)
R3Y-SV8N
P. 2 / 3
EM-8954 Rev.1
COMPONENT IDENTIFICATION
•
Conversion Rate
: SW3
SW
CONVERSION RATE
100 ms (
*
)
50 ms
20 ms
10 ms
SW3-1
OFF
ON
OFF
ON
SW3-2
OFF
OFF
ON
ON
(*) Factory setting
■
SIDE DIP SW
•
Input Range
: SW1, SW2 (selectable per 4 channels)
INPUT 1 through INPUT 4 (SW1)
INPUT 5 through INPUT 8 (SW2)
RANGE
1
2
3
4
OFF
OFF
OFF
OFF
-10 – +10V (*)
ON
OFF
OFF
OFF
-5 – +5V
ON
ON
OFF
OFF
0 – 10V
OFF
OFF
ON
OFF
0 – 5V
ON
OFF
ON
OFF
1 – 5V
RUN LED
ERR LED
■
FRONT VIEW
■
SIDE VIEW
• Pin Assignment
B
20
A
20
B
1
A
1
Input Connector
Range
Input 1-4 (SW1)
or
Input 5-8 (SW2)
ON
8
7
6
5
4
3
2
1
SW1
SW2
ON
8
7
6
5
4
3
2
1
Conv.
Rate
SW3
ON
4
3
2
1
■
STATUS INDICATOR LED
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with the input circuit abnormality (AD
converter response failure);
Green in normal operating conditions.