WIRING INSTRUCTIONS

 

TIGHTENING TORQUE

Separable screw terminal wiring screw: 0.5 N·m
Separable screw terminal fixing screw: 0.5 N·m

 

SOLDERLESS TERMINAL  unit: mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.  
Applicable wire size: 0.25 to 0.75 mm

2

Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.

3.2 (.13) dia.

12 (.47) max.

6 max

.

(.24)

3 (.12) max.

 

HOW TO REMOVE SEPARABLE SCREW TERMINAL

The terminal block is separable in two pieces.  Evenly loos-
en two screws on top and bottom of the terminal block to 
separate.

 

HOW TO ATTACH CJC SENSOR

In re-attaching once removed CJC sensor, connect it to ter-
CJn and COMn as shown below. 
A RTD is attached on the REAR surface of the CJC sensor.
In order to measure accurate reference junction tempera-
ture, be sure to connect the sensor to terminal COMn with 
its upside FRONT surface.

+CJn

COMn

CJC sensor
REAR surface

RTD

FRONT surface

PC CONFIGURATOR

The following parameter items can be set with using PC 
Configurator Software (model: R30CFG).
Refer to the users manual for the R30CFG for detailed op-
eration of the software program.

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

SETTING RANGE

DEFAULT
SETTING

Unused setting

CH enabled
CH disabled

CH enabled

Input Type

K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)
R
S
C (WRe 5-26)
N
U
L
P (Platinel II)
 (PR)

K (CA)

Burnout

Upscale
Downscale
None

Upscale

CJC

Enabled
Disabled

Enabled

Unit

degC
degF
K

degC

Fine zero adjustment -320.00 – +320.00 (%) 0.00 (%)
Fine gain adjustment -3.2000 – +3.2000

1.0000

Zero base

-3 200.0 – +3 200.0 
(degC, K)
-32 000 – +32 000 
(degF)

0.0

Full base

-3 200.0 – +3 200.0 
(degC, K)
-32 000 – +32 000 
(degF)

0.0

Scaled range Zero

-32 000 – +32 000

0

Scaled range Span

-32 000 – +32 000

10 000

 

CHANNEL BATCH SETTING

PARAMETER

SETTING RANGE

DEFAULT
SETTING

Conversion rate

250 ms
500 ms

500 ms

Simulate input

Normal input
Simulated data

Normal input