COMPONENT IDENTIFICATION

SW2

SW1

ON

1

2

3

4

5

6

7

8

ON

ON

1

2

3

4

5

6

7

8

SW3

1

2

3

4

5

19
20
21
22

15
16
17
18

23
24
25
26
27
28

6
7
8
9

10
11
12
13
14

1
2
3
4

■ 

FRONT VIEW

ERR LED

RUN LED

■ 

SIDE VIEW

Range
Input 1-4 (SW1)

  or

Input 5-8 (SW2)

Conv.

Rate

Functions

 

SIDE DIP SW

(*) Factory setting

• Input Range: SW1, SW2 

(selectable per 4 channels)

INPUT 1 through INPUT 4 (SW1)

RANGE

INPUT 5 through INPUT 8 (SW2)

1

2

3

4

OFF

OFF

OFF

OFF

-50 – +50V (*)

ON

OFF

OFF

OFF

-25 – +25V

OFF

ON

OFF

OFF

0 – 50V

ON

ON

OFF

OFF

0 – 25V

• Conversion Rate: SW3-1, 3-2

SW

CONVERSION RATE

160 ms (

*

)

80 ms

40 ms

20 ms

SW3-1

OFF

ON

OFF

ON

SW3-2

OFF

OFF

ON

ON

Note:  Be sure to set unused SW1-5 through 1-8, SW2-5 

through 2-8, SW3-3 and 3-4 to OFF.

 

STATUS INDICATOR LED

RUN indicator:

 Bi-color (red/green) LED;

Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

ERR indicator:

 Bi-color (red/green) LED;

Red with input circuit abnormality (AD con-
verter response failure);
Green in normal operating conditions.

PC CONFIGURATOR

With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Zero Scale

-32000 to +32000

0

Full Scale

-32000 to +32000

10000

Zero Adjust

-320.00 to +320.00

0.00

Full Adjust

-32000 to +32000

1.0000

Unused

0: Enable
1: Disable

0: Enable