R3-RS8B

P. 2 / 3

EM-8341

COMPONENT IDENTIFICATION

n

SIDE DIP SW

RTD Type

: SW1, SW2 (selectable per 4 channels)

SW2

SW1

ON

1

2

3

4

5

6

7

8

ON

ON

1

2

3

4

5

6

7

8

SW3

1

2

3

4

5

19
20
21
22

15
16
17
18

23
24
25
26
27
28

6
7
8
9

10
11
12
13
14

1
2
3
4

FRONT VIEW

ERR LED

RUN LED

SIDE VIEW

Input 1-4 (SW1)

  or

Input 5-8 (SW2)

RTD

Conv.Rate

Temp. Unit

Burnout

n

n

 

INPUT 1 through INPUT 4 (SW1)

 

INPUT 5 through INPUT 8 (SW2) 

RTD

 

1 2 3 4

 

OFF 

OFF 

OFF 

OFF 

Pt 100 (*)

 

    

(JIS ’97, IEC)

 

ON 

OFF 

OFF 

OFF 

Pt 100

 

 

 

 

 

(JIS ’89)

 

OFF 

ON 

OFF 

OFF 

JPt 100

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

DIMENSIONS  mm (inch)

TERMINAL

COVER

5

19
20
21
22

15
16
17
18

23
24
25
26
27
28

6
7
8
9

10
11
12
13
14

1
2
3
4

130 (5.12)

27.5 (1.08)

109 (4.29)

POSITIONING

GUIDE

28–M3

SCREW

6.2

(.24)

n

STATUS INDICATOR LED

RUN indicator

: Bi-color (red/green) LED; 

   

Red when the bus A operates normally;

   

Green when the bus B operates normally;

   

Amber when both buses operate normally.

ERR indicator

: Bi-color (red/green) LED; 

   

Red with burnout;

   

Green in normal operating conditions.

Burnout

: SW3

Temperature Unit

: SW3

Conversion Rate

: SW3

 SW3-1 

BURNOUT

 

OFF 

Upscale (*)

 ON  Downscale

 

SW3-2 

TEMP. UNIT

 

OFF 

°C (*)

 

ON 

°F

SW

                         

CONV. RATE

160

80

40

20

SW3-3

OFF(*)

ON

OFF

ON

SW3-4

OFF(*)

OFF

ON

ON

(*) Factory setting