OUTPUT DATA DESCRIPTIONS

Four alarm setpoints are selectable per each input. Two (2)
word (16 bit × 2) data is transmitterd to the PLC or the host
device via the R3 network module.

0

15

Alarm 1

Alarm 2

Input 1

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 2

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 3

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 4

Alarm 3

Alarm 4

0

15

Alarm 1

Alarm 2

Input 5

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 6

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 7

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 8

Alarm 3

Alarm 4

0

+1

0

15

Alarm 1

Alarm 2

Input 1

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 2

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 3

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 4

Alarm 3

Alarm 4

0

15

Alarm 1

Alarm 2

Input 5

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 6

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 7

Alarm 3

Alarm 4

Alarm 1

Alarm 2

Input 8

Alarm 3

Alarm 4

0

+1

ALARM SETTING

The following parameters are programmable using the PC 
Configurator Software (model: R3CON).

 

ALARM TRIP POINT (-15.00 to +115.00%)

Four alarm setpoints are selectable per each input.

 

ALARM TYPE (High or Low)

High or Low alarm is selectable for each alarm trip point.
High alarm:  An alarm is set when the input signal goes 

above the setpoint. 

Low alarm:  An alarm is set when the input signal goes be-

low the setpoint.

 

DEADBAND (HYSTERESIS)

  (0.00 to 100.00%; factory set to 5.00)

Deadband (deviation between the points where the alarm is
set and reset) is selectable for each alarm trip point.

 

POWER ON DELAY TIME

  (0.0 to 99.0 seconds; factory set to 5.0)

The alarm output start functioning in the preset time after
the power has been turned on.
This setting is common to all four points.

 

ALARM ON DELAY TIME

  (0.0 to 99.0 seconds; factory set to 1.0)

The alarm output is set when the preset time elapses after 
the input has entered in the alarm range.
This setting is common to all four points.

 

ALARM HOLD TIME

  (0.0 to 99.0 seconds; factory set to 1.0)

The alarm output is held for the preset time even if it is 
reset in shorter time.
This setting is common to all four points.