COMPONENT IDENTIFICATION
SW2
SW1
ON
1
2
3
4
5
6
7
8
ON
ON
1
2
3
4
5
6
7
8
SW3
1
2
3
4
5
19
20
21
22
15
16
17
18
23
24
25
26
27
28
6
7
8
9
10
11
12
13
14
1
2
3
4
■
FRONT VIEW
ERR LED
RUN LED
■
SIDE VIEW
Range
Input 1-4 (SW1)
or
Input 5-8 (SW2)
Conv.
Rate
Functions
■
SIDE DIP SW
(*) Factory setting
•
Input Range: SW1, SW2 (selectable per 4 channels)
INPUT 1 through INPUT4 (SW1)
RANGE
INPUT 5 through INPUT8 (SW2)
1
2
3
4
OFF
OFF
OFF
OFF
-10 – +10V (*)
ON
OFF
OFF
OFF
-5 – +5V
OFF
ON
OFF
OFF
-1 – +1V
ON
ON
OFF
OFF
0 – 10V
OFF
OFF
ON
OFF
0 – 5V
ON
OFF
ON
OFF
1 – 10V
OFF
ON
ON
OFF
0 – 1V
•
Conversion Rate: SW3
SW
CONVERSION RATE
160 ms (
*
)
80 ms
40 ms
20 ms
SW3-1
OFF
ON
OFF
ON
SW3-2
OFF
OFF
ON
ON
Note: Be sure to set unused SW1-5 through 1-8, SW2-5 through
2-8, SW3-3 and 3-4 to OFF.
■
STATUS INDICATOR LED
RUN indicator:
Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator:
Bi-color (red/green) LED;
Red with the input abnormality;
Green in normal operating conditions.