R1MS-GH3

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5671 Rev.6  P. 6 / 8

 

DATA ADDRESS

ADDRESS

DATA FORMAT

NAME

Coil (0X)

1 – 32

bit

DO: Alarm (Only Address 10001 is enabled.)

33 – 40

bit

Cold junction compensation SW (0: Disable, 1: Enable) *

1

Input Status (1X)

1 – 32

bit

DI: Trigger contact input (Only Address 10001 is enabled.)

33 – 40

bit

ADC overrange

Input Register (3X)

1 – 8

I

AI per channel in engineering unit (DC: × 1000, TC: × 10)

17 – 32

F

AI per channel in engineering unit

33 – 48

F

Calibrated voltage value

49 – 64

F

Cold junction temperature *

2

65 – 72

F

Temperature measured at Ch.1 thr. 4

81 – 88

I

Channel status

513

I

Bit

System Status

0 to 5

Reserved for system use

6

E

2

PROM diagnostics (0: Normal, 1: Error)

7

ADC error (0: Normal, 1: Error)

8 to 15 Reserved for system use

514 – 521

B16

Model No. 

522 – 529

B16

Serial No.

530 – 537

B16

Hardware version No.

538 – 545

B16

Firmware version No.

Holding Register (4X)

49 – 50

F

Input filter time constant (seconds) *

3

145 – 152

I

I/O type No

514

I

Burnout type (0: No burnout, 1: Upscale, 2: Downscale) *

1

515

I

Line noise filtering type (0: 50/60 Hz, 1: 50 Hz, 2: 60 Hz) *

1

bit =1bit, I = 16-bit integer, F = 32-bit floating, B16 = 16-byte character
*1. Changeable only when the mode SW is set to 0 for R1MS-GH3.
*2. Thermocouple input only.
*3. Effective for large noise in the input signal. 0 sec. = No Filtering

Sign

Address n+1

• 32-bit Floating

Address n

Exponent

Mantissa

 INPUT DATA

Summary of Contents for R1MS-GH3

Page 1: ...re is downloadable at M System s web site http www m system co jp POINTS OF CAUTION POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V AC rating 85 264V 47 66 Hz approx 9VA 24V DC rating 24V 10 approx 3 5W GENERAL PRECAUTIONS Before you remove the module turn off the power supply input signal and ou...

Page 2: ...tion than 50 60 Hz setting Note 3 Factory default setting is 1 INSTALLATION DIN RAIL MOUNTING Set the body so that its DIN rail adaptor is at the bottom Pull down the DIN rail adaptor Position the upper hook at the rear side on the DIN rail and push in the lower Push back the DIN rail adaptor WALL MOUNTING Set the body so that its DIN rail adaptor is at the bottom Pull down the DIN rail adaptor Re...

Page 3: ...rrent inputs into voltage However use of REM3 is not recommended when TC inputs are mixed because the heat developed on and around the REM3 affects the cold junction compensation performance ext wire ext wire ext wire ext wire ext wire ext wire ext wire ext wire Power Circuit Shielded Twisted pair Cable To Other I O Modules Jumper 1 FG U V POWER D SUB CONNECTOR JACK CONFIGURATOR Isolated Analog In...

Page 4: ...ire size 0 75 to 1 25 mm2 AWG19 to 16 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co ltd 6 max 24 3 12 max 3 2 13 dia mm inch EUROTYPE CONNECTORTERMINAL Power input Modbus Applicable wire size 0 2 to 2 5 mm2 AWG24 to 12 Stripped length 7 mm COMMUNICATION CABLE CONNECTIONS R1M T1 T2 T3 T4 R1M T1 T2 T3 T4 T1 T2 T3 T4 R1M CONNECTOR RS 232 C RS 485 1 1 1 Internal terminating ...

Page 5: ...lave 04 Read Input Registers X Collected data from the field by the slave 05 Force Single Coil X Digital output from the slave 06 Preset Single Registers X General purpose register within the slave 07 Read Exception Status 08 Diagnostics 09 Program 484 10 Poll 484 11 Fetch Comm Event Counter Fetch a status word and an event counter 12 Fetch Comm Event Log A status word an event counter a message c...

Page 6: ...rature measured at Ch 1 thr 4 81 88 I Channel status 513 I Bit System Status 0 to 5 Reserved for system use 6 E2 PROM diagnostics 0 Normal 1 Error 7 ADC error 0 Normal 1 Error 8 to 15 Reserved for system use 514 521 B16 Model No 522 529 B16 Serial No 530 537 B16 Hardware version No 538 545 B16 Firmware version No Holding Register 4X 49 50 F Input filter time constant seconds 3 145 152 I I O type N...

Page 7: ...tion is enabled or disabled for thermocouple input 0 Disable 1 Enable Others Reserved For system s use INPUT REGISTERS DESCRIPTION Indicates I O type for each channel The data are 16 bit integer values MODEL I O I O TYPE SELECTION USABLE RANGE NOTES R1MS GH3 R2M 2G3 DC input 0x00 10 to 10 V 10 to 10 V R1M GH2 DC input 0x00 20 to 20 V 22 7 to 22 7 V ATT SW ON 0x01 5 to 5 V 5 6 to 5 6 V ATT SW ON 0x...

Page 8: ...P SW setting Check that all switches are set correctly ADJUSTMENT PROCEDURE This unit is calibrated at the factory to meet the ordered specifications therefore you usually do not need any cali bration MAINTENANCE Regular calibration procedure is explained below CALIBRATION Warm up the unit for at least 10 minutes Apply 0 25 50 75 and 100 input signal Check that the output signal for the respective...

Reviews: