TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the top of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

3

4

5

6

2

1

8

7

80 (3.1

5)

50 (1.97)

103 (4.06)

123 (4.84)

[3.3 (.13)]

80 (3.1

5)

20 (.79)

40 (1.57)

50 (1.97)

7.8 (.31)

CLAMP

(top & bottom)

DIN RAIL

35mm wide

2

4.5 (.18) dia.

MTG HOLE

15 (.59) deep

8

M3.5

SCREW

• When mounting, no extra space is needed between units.

 

CONNECTION DIAGRAM

+

+

INPUT

3

OUTPUT

4

1

2

U(+)

V(–)

POWER

7

8

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit as explained earlier (ITEM 
07 and 08).

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.