MXV
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1717 Rev.11 P. 3 / 4
■
SELECTING INPUT RANGE
[E.G.] -5.0 to 5.0V DC
1) Program Mode
Set ITEM 01 – DATA 2 to turn the unit into Program
Mode.
2) 0% Input Voltage
Choose ITEM 14 – DATA -5.0.
3) 100% Input Voltage
Choose ITEM 15 – DATA 5.0.
4) Monitor Mode
Set ITEM 01 – DATA 1 to turn the unit into Monitor
Mode.
5) PV Indication
Press ITEM UP or DOWN key until ITEM display indi-
cates “P”.
■
SELECTING OUTPUT RANGE
[E.G.] -10.0 to 0.0V DC
1) Turn the unit into Program Mode.
2) 0% Output Voltage
Choose ITEM 16 – DATA -10.0.
3) 100% Output Voltage
Choose ITEM 17 – DATA 0.0.
4) Turn the unit into Monitor Mode.
5) Set to ITEM P.
■
DISPLAY RANGE SCALING
[E.G.] PV display range -10.0 to 10.0 modified to show -6500
to 350
1) Turn the unit into Program Mode.
2) Decimal Point Position
Choose ITEM 11 – DATA 0.
3) 0% Scaling Value
Choose ITEM 09 – DATA -6500.
(Negative [–] range is identified with the PL1 turned on.)
4) 100% Scaling Value
Choose ITEM 10 – DATA 350.
5) Turn the unit into Monitor Mode.
6) Set to ITEM P.
■
RESET ALL SETTINGS
Returning the unit into the default settings.
1) Turn the unit into Reset Mode.
Set ITEM 01 – DATA 3 to turn the unit into Reset Mode.
2) Call up the Reset menu.
Choose ITEM 19 – DATA 1. (Press DATA UP key.)
3) Resetting Enable
Double-click DATA DOWN key. DATA 0 is displayed af-
ter the initialization is complete.
4) Turn the unit into Monitor Mode.
If necessary, go to Moving Average and other adjustments.
Set the unit to Monitor Mode other than for programming.
■
PROGRAMMING ERROR LED, PL2
When the PL2 is turned on, identify the cause of error with
ITEM 02 (Status Indication).
REF.
ERROR
0
Normal
9
Display range scaling: 0% Setting > 100% Setting, or
Overrange: See ITEM 09 / 10.
14
Input range setting: 0% Setting > 100% Setting
See ITEM 14 / 15.
16
Output range setting: 0% Setting > 100% Setting
See ITEM 16 / 17.
99
Memory error: Initialize all the settings of the unit
by operating ITEM 19 and program the unit again.