MXCB
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1745 Rev.5 P. 5 / 6
ITEM
MDF.
CODE
DATA
CONTENTS
DEFAULT
26
2
0, 1
STOP input logic
0 : True at LOW or Shortcircuit
(Soft-Terminal input)
1 : True at HIGH or Opencircuit
0 *
2
29
2
-1.00 – 1.00
Output code V1
0% output voltage (V) *
3
-1.00
30
2
-1.00 – 1.00
100% output voltage (V) *
3
1.00
29
2
-10.0 – 10.0
Output code V2
0% output voltage (V) *
3
-10.0
30
2
-10.0 – 10.0
100% output voltage (V) *
3
10.0
29
2
0.0 – 20.0
Output code Z1
0% output current (mA) *
3
4.0
30
2
0.0 – 20.0
100% output current (mA) *
3
20.0
31
32
2
2
-15.0 – 114.9
-14.9 – 115.0
Lower output limit
Upper output limit
0.0
100.0
33
3
0, 1
Reset all settings *
4
0
34
N/A
---
ROM version
---
*1. Of the range set in ITEM 06/07. ITEM 08 < ITEM 09.
*2. Use the default setting when combining with the ST/STL.
*3. ITEM 29 < ITEM 30.
*4. Press DATA UP key and choose DATA 1. Double-click DATA DOWN key. The display shows DATA 0 after the initialization is
complete.
■
SELECTING OUTPUT RANGE
[E.G.] -10.0 to 0.0V DC
1) Turn the unit into Program Mode.
2) 0% Output Voltage
Choose ITEM 29 – DATA -10.0.
3) 100% Output Voltage
Choose ITEM 30 – DATA 0.0.
4) Turn the unit into Monitor Mode.
5) Set to ITEM P.
■
DISPLAY RANGE SCALING
[E.G.] PV display range -10.0 to 10.0 modified to show -6500
to 350
1) Turn the unit into Program Mode.
2) Decimal Point Position
Choose ITEM 10 – DATA 0.
3) 0% Scaling Value
Choose ITEM 08 – DATA -6500.
(Negative [–] range is identified with the PL1 turned on.)
4) 100% Scaling Value
Choose ITEM 09 – DATA 350.
5) Turn the unit into Monitor Mode.
6) Set to ITEM P.
■
RESET ALL SETTINGS
Returning the unit into the default settings.
1) Turn the unit into Reset Mode. Choose ITEM 01 – DATA
3.
2) Call up the Reset menu.
Choose ITEM 33 – DATA 1. (Press DATA UP key.)
3) Resetting Enable
Double-click DATA DOWN key. DATA 0 is displayed af-
ter the initialization is complete.
4) Turn the unit into Monitor Mode.
If necessary, go to Moving Average and other adjustments.
Set the unit to Monitor Mode other than for programming.