13.  PARAMETER ITEMS COMMON TO MODBUS AND PU-2x

13.1.  Note for parameter items

ITEM

DESCRIPTION

MODBUS TYPE

I16=Integer type data,
I32=Long type data (little endian)

VALUE RANGE

Value with one decimal place is multiplied by 10 and handled as an integer.
Value is used as is with one decimal place on PU-2x.

PU-2x DISPLAY

x represents a number.

R/W

R= Read only
R/W=Read and Write 

SAVE

Setting is saved for the item with ‘

’ in the [Save] column.

13.2.  Device information

MODBUS

ITEM

VALUE RANGE

INITIAL 

VALUE

PU-2x

R/W SAVE

ADDRESS TYPE

ITEM

DISPLAY

1

I16

Msp format
‘MSPxx – yz’ is expressed by 4-digits of xxyz

4013 to 5037

01

Model:x

R

2

I16

Firmware: Major version

0 to 9

02

Ver:x.y.z

R

3

I16

Firmware: Minor version

0 to 99

4

I16

Firmware: Revision

0 to 99

5 to 16

I16

x 12

Tag setting
 · ASCII code (0x20 to 07x7E) 
 · Stored in order from the head address 
 ·  On PU-2x, enter characters as needed and 

the rest, if any, is entered as space. 

ASCII code

(0x20 to 0x7E)

x 12 characters

blank

(0x20)

03

Tg.xxxx...xx R/W

17

I16

Analog input (%)

-25.0 to 125.0

04

Inp:x

R

18

I16

Position setpoint (%)  *

1

-5.0 to 105.0

05

Tar:x

R

19

I16

Position (%)  *

1

 

-5.0 to 105.0

06

Pos:x

R

*1  The ratio to the operation distance (i.e. a distance between the lower-stop position and the upper-stop position).

13.3.  Diagnostics

MODBUS

ITEM

VALUE RANGE

INITIAL 

VALUE

PU-2x

R/W SAVE

ADDRESS TYPE

ITEM

DISPLAY

21

I32

Total power-on time (hour)

0 to 596523

0

07

PowTm:x

R

23

I32

Total operation time (hour)

0 to 596523

0

08

MovTm:x

R

25

I32

Total operation distance  
(1 count per operation distance *

2

)

0 to 99999999

0

09

Dist:x

R

27

I32

No. of times of motor start actions

0 to 99999999

0

10

Strt:x

R

29

I32

No. of times of motor reverse actions

0 to 99999999

0

11

Rvrs:x

R

31

I32

No. of times of motor restart

0 to 99999999

0

12

Rtry:x

R

33

I32

No. of times when the duty cycle per minute 
exceeded 50%

0 to 99999999

0

13

Over:x

R

35

I16

Duty cycle (%) per minute

0.0 to 100.0

0.0

14

Duty:

R

36

I16

Time ratio (%) of - 10% position  *

3

0.0 to 100.0

0.0

15

Pos0R:x

R

37

I16

Time ratio (%) of 10 - 20% position  *

3

0.0 to 100.0

0.0

16

Pos10R:x

R

38

I16

Time ratio (%) of 20 - 30% position  *

3

0.0 to 100.0

0.0

17

Pos20R:x

R

39

I16

Time ratio (%) of 30 - 40% position  *

3

0.0 to 100.0

0.0

18

Pos30R:x

R

40

I16

Time ratio (%) of 40 - 50% position  *

3

0.0 to 100.0

0.0

19

Pos40R:x

R

41

I16

Time ratio (%) of 50 - 60% position  *

3

0.0 to 100.0

0.0

20

Pos50R:x

R

42

I16

Time ratio (%) of 60 - 70% position  *

3

0.0 to 100.0

0.0

21

Pos60R:x

R

Summary of Contents for MSP40

Page 1: ...BLE CONNECTIONS 6 7 OUTPUT STEM STROKES 7 8 SEAL SPRING CONTRACTION AND THRUST 7 9 COMBINATION WITH VALVE 8 10 AUTO SETUP MODE 9 11 PROGRAMMING UNIT MODEL PU 2x 12 12 MODBUS COMMUNICATION 13 13 PARAME...

Page 2: ...failure to observe the pre cautions could result in personal injury or damage to the property WARNING Remove power supply to the actuator before wiring to the unit It could cause electric shock Do not...

Page 3: ...to withstand all vibrations M System does not guarantee long term use of the unit even with small vibrations Please use the unit only after evaluating in an actual installation environment Par ticula...

Page 4: ...l Spring Stepping Motor Potentiometer Cover Nut Output stem Screw Figure 1 Component identification MSP40 MSP50 DA NC IN FE1 UPP UPP LOW LOW ALM ALM 24V GND COM OUT DB DG PWR UPPER LOWER INP STA COM A...

Page 5: ...h 20 mA DC input ON Direct Output stem goes DOWN with 20 mA DC input SW1 4 OFF Output stem moves while the manual operation button is pressed in Manual Operation mode ON Output stem moves inch by inch...

Page 6: ...retract UP extend DOWN alarm and or output signals as necessary Modbus communication allows operation without analog input and monitoring of the operation status of the unit DA DB DG IN COM OUT 24V GN...

Page 7: ...RACTION AND THRUST Thrust and Seal Spring Contraction MODEL RATED THRUST N THRUST WHEN VALVE IS SEATED N THRUST WHEN AUTO SEUP IS COMPLETE N AJUSTABLE MAX CONTRACTION MAX THRUST N MAX THRUST WHEN OUTP...

Page 8: ...void such a situation select an appropriate combination of an actuator and a valve to secure an enough opera tion distance In the example below the maximum stroke is 20 mm and thus the preferable oper...

Page 9: ...h back to Automatic Operation mode Note that the actuator immediately starts to operate in accordance with a value of input signal DO NOT touch the output stem and its vicinity as it may cause serious...

Page 10: ...ositions then stops to end Auto setup 4 Lower Upper seal springs MSP50 only 1 The output stem goes down until the valve contacts the seat surface Auto setup is interrupted if the valve reaches the low...

Page 11: ...newly set the upper end position To complete the fine adjustment Lower end side Turn SW1 5 from OFF to ON then to OFF again to newly set the lower end position Upper end side Turn SW1 6 from OFF to ON...

Page 12: ...e display of PU 2x comes on by power supplied to the actuator unit 3 To display a target item press ITEM then N N N represents numerical number 0 to 9 Alternatively use UP or DOWN button to shift to t...

Page 13: ...ven if the address is writable make sure to set Modbus Operation mode address 111 in advance to enable writing ADDRESS MAP Refer to 13 PARAMETER ITEMS COMMON TO MODBUS AND PU 2x for Modbus address map...

Page 14: ...04 Inp x R 18 I16 Position setpoint 1 5 0 to 105 0 05 Tar x R 19 I16 Position 1 5 0 to 105 0 06 Pos x R 1 The ratio to the operation distance i e a distance between the lower stop position and the up...

Page 15: ...times when the duty cycle per minute exceeded 50 1 Clear 0 1 0 26 AccumClr x R W 52 I16 Time ratio of respective positions 1 Clear 0 1 0 27 PosRClr x R W 53 I16 Clear all diagnostics 1 Clear 0 1 0 28...

Page 16: ...98 0 44 OpnSig x R W 136 I16 Extend DOWN signal position 5 0 to 25 0 2 0 45 ClsSig x R W 137 I16 Deadband 0 1 to 5 0 0 3 46 DBand x R W 138 I16 Restart limiting timer sec 0 0 to 30 0 1 5 47 Restart x...

Page 17: ...guration mode Stops Modbus input Monitor mode Stops Modbus input mode Follows Modbus input Address 101 Configuration mode Stops ON N A 2 Monitor mode 4 Moves by button operation 1 Configurable on PU 2...

Page 18: ...acement contact M System or our representatives LUBRICATION There is no need of oiling the Mini Top electronic actuator in normal operating conditions REGULAR TEST RUNNING If the valve is not frequent...

Reviews: