MAINTENANCE

Check M-RESTER periodically. Many cases of lightning are 
ignored, and even lightning at a far distance often causes
inductive surges.
We recommend that you check your M-RESTER about twice 
a year, before and after the rainy season. Check whenever 
you experience a strong lightning occurence.
Checking procedure is explained in the following:

 

CHECKING

WIRING

• Make sure that wiring is done as instructed in the con-

nection diagram.

• Make sure that the Ground terminal (G) is connected to 

the metallic housing of protected equipment.

• Make sure that the Ground terminal (G) is grounded to 

earth.

ALARM INDICATOR LED

• Check that the power is suplied.
• When the green LED is off despite that power is sup-

plied, the discharge element may be failed. Replace the 
M-RESTER.

DISCHARGE FUNCTION

Remove all wiring connected to M-RESTER and test its dis-
charge capability as follows:

• Check resistance across the following terminals (infinite 

standard).

          Terminals (U) – (V), (U) – (G), (V) – (G)

• Check that discharging occurs across the following termi-

nals with a 1000V DC megger. (Indicator of the megger 
reaches over-scale.)

          Terminals (U) – (V), (U) – (G), (V) – (G)

LEAKAGE CURRENT (between lines)

Apply supply voltage across the terminals (U) – (V) with 
no load, and measure current at the terminal (U). (≤5mA 
standard)

• If any of the above tests shows negative, replace the 

MRESTER.