MAINTENANCE

Check M-RESTER periodically. Many cases of lightning are 
ignored, and even lightning at a far distance often causes 
inductive surges.  We recommend that you check your M-
RESTER about twice a year, before and after the rainy 
season. Check whenever you experience a strong lightning 
occurence.
Checking procedure is explained in the following:

 

CHECKING

WIRING

• Make sure that wiring is done as instructed in the con-

nection diagram.

• Make sure that the Ground terminal (G) is connected to 

the metallic housing of protected equipment.

• Make sure that the Ground terminal (G) is grounded to 

earth.

ALARM INDICATOR LED

• M-RESTER is designed to protect the equipment even 

when subjected to a lightning surge exceeding its dis-
charge current capacity to certain extent. However, in 
such a case, the insulation of its discharge element may 
fail. When it happens, the fuse is blown and the green 
LED on the front panel of M-RESTER turns off.

• Maximum surge voltage in this condition may be up to 

800V.

• When the green LED is off despite that power is supplied, 

replace the M-RESTER. 

DISCHARGE FUNCTION

• Remove all wiring connected to M-RESTER and test its 

discharge capability as follows:

• Check resistance across the following terminals (infinite 

standard). Terminals (U) – (V), (U) – (G), (V) – (G)

• Check that discharging occurs across the following ter-

minals with a 500V DC megger. (Indicator of the megger 
reaches over-scale.)

          Terminals (U) – (V), (U) – (G), (V) – (G)

LEAKAGE CURRENT (between lines)

Apply supply voltage across the terminals (U) – (V) with 
no load, and measure current at the terminal (U). (≤5mA 
standard)

• If any of the above tests shows negative, replace the M-

RESTER.