DIP SWITCH SETTING

Choose the output function: High/Low output, normal output proportional to the input 1, or loop test output of 0%, 50% and 
100%.
Set the DIP switch to appropriate positions before turning on the power supply.  No change in the switch positions is valid 
while the power is supplied.

OUTPUT

SW1-1

SW1-2

SW1-3

SW1-4

STAT1 LED

STAT2 LED

High signal (*)

OFF

OFF

OFF

OFF

ON

OFF

Low signal

ON

OFF

OFF

OFF

ON

OFF

Input 1

*1

ON

OFF

OFF

ON

OFF

    0%

*1

*1

ON

OFF

OFF

ON

  50%

*1

*1

OFF

ON

Blinking

ON

100%

*1

*1

ON

ON

ON

ON

(*) Factory setting
*1. ON/OFF position is irrelevant.

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

3) Input:  Check that the input voltage is within 0 – 100% of 

full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following. 

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes. Be sure to start with the Input 1 
adjustment.

1) Turn all DIP switches to OFF positions. (Selecting High 

signal)

2) Set Input 2 lower than 0%.
3) Input 1 ZERO (ZERO1):  Apply 0% input and adjust out-

put to 0%.

4) Input 1 SPAN (SPAN1):  Apply 100% input and adjust 

output to 100%.

5) Check Input 1 ZERO adjustment again with 0% input.
6) When ZERO value is changed, repeat the above proce-

dure 3) – 5).

7) Set Input 1 lower than 0%.
8) Input 2 ZERO (ZERO2):  Apply 0% input and adjust out-

put to 0%.

9) Input 2 SPAN (SPAN2):  Apply 100% input and adjust 

output to 100%.

10) Check Input 2 ZERO adjustment again with 0% input.
11) When ZERO value is changed, repeat the above proce-

dure 8) – 10).

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.