TERMINAL CONNECTIONS

Connect the unit as in the diagram below.
Be sure to cross-wire between the ground terminal (G) and 
that of the protected equipment.

TELEMETER

PLC

XMTR

M-RESTER

PROTECTED

EQUIPMENT

M-RESTER

P1

P2

P8

G

COM

RELAY

METAL

HOUSING

FIELD

S1

S2

S8

COM

S1

S2

S8

G

G

COM

P1

P2

P8

COM

 

GROUNDING

M-RESTER

PROTECTED

EQUIPMENT

G

G

CROSSOVER WIRE

GROUNDING

(100 ohms or less)

A crossover wire between M-RESTER ground and the ground or 

metallic housing of the equipment is required for protection.

If the protected equipment has no ground terminal, ground the 

M-RESTER only.

 

WIRING

PROTECT

SIDE

MONITOR

1

2

3

4

SURGE

SIDE

S1

S2

S3

S4

S5

P1

P2

P3

P4

P5

When the connections of serge and protecting sides get bun-
dled, the protection effect decreases.  Be sure to wire them 
separately.
Wiring to the terminals, please install wires according to 
the above figure.

MAINTENANCE

Check M-RESTER periodically.  Many cases of lightning are 
ignored, and even lightning at a far distance often causes 
inductive surges.
We recommend that you check your M-RESTER about twice 
a year, before and after the rainy season.  Check whenever 
you experience a strong lightning occurrence.
Checking procedure is explained in the following:

 

CHECKING

WIRING

1) Make sure that wiring is done as instructed in the con-

nection diagram.

2) Make sure that the ground terminal (G) is connected to 

the metallic housing of protected equipment.

3) Make sure that the ground terminal (G) is grounded to 

earth.

DISCHARGE ELEMENTS

Approximate checking can be conducted as following.

• MDR2-8xA (with LED monitor)

1) Make sure that the front LED monitor turns OFF while 

the discrete signal is ON.

2) When leakage current exceeds the rating (5μA), the LED 

becomes brighter gradually.  In this case, please replace 

the unit.

3) When the discrete signal is unable to be ON, take the 

same procedure as MDR2-8xN.

• MDR2-8xY (without LED monitor)

Remove all wiring connected to M-RESTER when you test 
the discharge elements.

1) Check resistance across the following terminals on the 

high resistance range of multimeter and confirm no con-

duction. (The meter will show 10MΩ or greater.)

     

Terminals (P1) or (P2) or (P3) or (P4) or (P5) or (P6)  

     

or (P7) or (P8) – (COM), (COM) – (G)

When measuring across the Px to COM, apply the positive 
voltage for MDR2-8N or negative voltage for MDR2-8P with 
multimeter.

1) Check that discharging occurs across the same terminals 

with a 500V DC/1000 MΩ insulation tester.  (The tester 

will show 20 MΩ or less.)

2) If any of the above tests shows negative, replace the 

M-RESTER.