MD73W

EM-8061  Rev.4  P. 2 / 4

INSTALLATION

Mount the unit on a DIN rail.  Once installed, do not move it to another DIN rail.

 

MOUNTING THE UNIT ON A DIN RAIL

A) Hang the upper hook of the DIN rail mounting adaptor

at the rear side of unit, on the DIN rail.

B) Push in the lower in keeping pressing the unit to the DIN 

rail.

C) DIN rails generally have slight individual variability in

size.  If you find it difficult to push in the lower part, go

back to (A) and hang the upper part more deeply onto the

rail and try (B) again.

A

DIN Rail

B

 

REMOVING THE UNIT

A) Push down the spring loader utilizing a minus screwdriv-

er.

B) Confirm that it is pulled enough down and pull out the

lower part of the unit.

C) Detach the upper part from the DIN rail.

A

B

Spring Loader

C

TERMINAL CONNECTION

Connect the unit as in the diagram below.
Be sure to ground the DIN rail on which the unit is mounted and cross-wire between the rail and FG terminal of the protected 
device as shown in Figure 1 in order to equalize the earth potential.
When the unit is connected with a device which has no FG terminal, ground the surge protector only.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

8
6
5
4

1
2
3
7

4

1

5

2

6

3

8

7

95 (3.74)

7

(.28)

98 (3.86)

[1.5 (.06)]

8–M3 EURO 

TERMINAL

DIN RAIL

(35 mm wide)

DIN RAIL

ADAPTOR

WIRE INSERTION ANGLE: approx. 20°

57 (2.24)

1.9 (.07)

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for MD73W

Page 1: ...ECIFICATIONS LINE TO LINE LINE TO EARTH Max continuous operating voltage Uc 32V 32V Voltage protection level Up 6kV 1 2 50 µs 60V 60V Leakage current Uc 5µA 5µA Response time 4 nsec 20 nsec Max discharge current Imax 20kA 8 20 µs 1 0kA 10 350 µs Nominal current IN 400mA Internal series resistance 2 2Ω 20 per line POINTS OF CAUTION ENVIRONMENT Indoor use When heavy dust or metal particles are prese...

Page 2: ... a minus screwdriv er B Confirm that it is pulled enough down and pull out the lower part of the unit C Detach the upper part from the DIN rail A B Spring Loader C TERMINAL CONNECTION Connect the unit as in the diagram below Be sure to ground the DIN rail on which the unit is mounted and cross wire between the rail and FG terminal of the protected device as shown in Figure 1 in order to equalize t...

Page 3: ...g DIN RAIL DIN RAIL ADAPTOR for grounding DIN RAIL Grounding DISCHARGE ELEMENT Receiver FG Transmitter FG 1 Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground Use a steel or copper rail 2 Be sure to ground the DIN rail Recommended grounding resistance 100Ω 3 Cross wire between the DIN rail and the metal housing of the protected dev...

Page 4: ... to the metal enclosure of protected device 3 Make sure that the surge protector is securely attached to the DIN rail and that the rail is grounded to earth DISCHARGE ELEMENT 1 Remove all wiring connected to the surge protector when you test the module 2 Check resistance across the following terminals on the high resistance range of multimeter and confirm no con duction Terminals 4 5 4 6 5 6 4 DIN...

Reviews: