EM-8228 Rev.3

P. 2 / 3 

MD-LC2

INSTALLATION

Detach the yellow clamps located at the top and bottom of the 

unit for separating the body from the base socket.

n

 DIN RAIL MOUNTING

Set the base socket so that 

its DIN rail adapter is at the 

bottom.  Hung the upper hook 
at the rear side of 

base socket on the DIN rail 
and push in the lower.  When 

removing the socket, push 

down the DIN rail

adapter utilizing screwdriver 

(–) and pull.

n

 WALL MOUNTING

Refer to the drawing in the 
next page.

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

Be sure to connect the shield wire to the Shield terminal (3 and 8) and ground the terminal 8 of the MD-LC2.

GROUNDING

A cross-over wire between M-RESTER and ground or metallic 
housing of equipment is required for protection.  When the 

protected equipment has no ground terminal, ground only 
the M-RESTER.

M-RESTER

2

11

4

12

M-RESTER

5

4

12

2

11

15

14

14

15

(PROTECTED EQUIPMENT)

9

1

10

8

7

3

6

7

9

Remote Sensing

Strain Gauge Transmitter LC2/LCS2

SHIELD

1

2

OUTPUT

8

7

POWER

EXC

INPUT

1

5

6

10

8

3

EXC +

EXC –

(+)

(–)

OUTPUT

Strain Gauge

(PROTECTED EQUIPMENT)

SHLD

4

5

10

11

6

9

3

S

+

S

G

SHLD

+

U(+)

V(–)

+

L1

L2

metal housing

Clamp

(top & bottom)

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

Shape and size of the base socket 
are slightly different with various 
socket types.

M-RESTER

PROTECTED

EQUIPMENT

G

G

CROSSOVER WIRE

GROUNDING

(100 ohms or less)

A crossover wire between M-RESTER ground and the ground or 

metallic housing of the equipment is required for protection.

If the protected equipment has no ground terminal, ground the
M-RESTER only.