TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

I/O PINS

17.5 (.69)

48 (1.89)

75 (2.95)

83 (3.27)

 

CONNECTION DIAGRAM

+

Installation Base

OUTPUT 1

6

7

8

9

10

11

+

+

OUTPUT 2

POWER

3

4

D

C

LOAD

SOURCE

CONNECTOR

*

k

l

CLAMP-ON SENSOR

*

Connector provided only for the CLSA-08 and CLSA-12.

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input:  Check the power input voltage.
3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.
(Output 1 and Output 2 are linked.)

1) ZERO:  Apply 0% input and adjust output to 0%.
2) SPAN:  Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

M8CTC

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5483  Rev.1  P. 2 / 4

Summary of Contents for M8CTC

Page 1: ...nt ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 0 to 55 C 32 to 131 F with relative humidity within 30 to 95 RH in order to ensure adequate life span and operation Be sure that the ventilation slits are not covered with ca bles etc WIRING Do not install cables close to noise sou...

Page 2: ...LIBRATE THE OUTPUT SIGNAL Use a signal source and measuring instruments of sufficient accuracy level Turn the power supply on and warm up for more than 10 minutes Output 1 and Output 2 are linked 1 ZERO Apply 0 input and adjust output to 0 2 SPAN Apply 100 input and adjust output to 100 3 Check ZERO adjustment again with 0 input 4 When ZERO value is changed repeat the above proce dure 1 3 MAINTENA...

Page 3: ...Weight 300 g 10 6 oz 36 1 41 dia 80 3 15 59 5 2 34 50 1 97 38 1 50 4 16 4 16 200 7 87 l k K L CLAMP ON CURRENT SENSOR screw terminal type CLSB Connection M3 screw terminal torque 0 5 N m Screw terminal Nickel plated steel Output wiring Use AWG 22 or thicker wires for the output Twist the paired wires extendable up to 30 meters 0 10A through 0 50A Use Sensor model No CLSB 05 Applicable cable diamet...

Page 4: ... 1 40 8 8 35 8 8 35 93 3 66 TERMINAL COVER detachable 35 dia 1 38 k k l l 2 M3 SCREW K L Note 1 The output values may vary depending on the accuracy of engagement at the clamp connection Note 2 The sensor is detachable up to 100 times approx Note 3 The sensor s mechanical construction may cause it to generate resonance sound However it does not affect the performance of the sensor M8CTC 5 2 55 Min...

Reviews: