TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

I/O PINS

17.5 (.69)

48 (1.89)

75 (2.95)

83 (3.27)

 

CONNECTION DIAGRAM

+

Installation Base

OUTPUT 1

6

7

8

9

10

11

+

+

OUTPUT 2

1

2

A

B

POWER

+

INPUT

Open Collector

Output Connection Examples 

+

6

7

+

Voltage Pulse

+

6

7

+

+

8

9

+

8

9

+

+

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input:  Check the power input voltage.
3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check that the load meets the specifications as 

described below:

    • Open collector: 50V DC @ 50mA max. (load ≤ 1kΩ)
    • 5V pulse: ≥ 1kΩ

  The output pulse width is as illustrated below.  Check 

specifications of the receiving device.

Open Collector

Voltage Pulse

OFF

ON

50%

50%

1 / f

50%

50%

1 / f

H Level

L Level

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.
(Output 1 and Output 2 are linked.)

1) ZERO:  Apply 5% input and adjust output to 5%.
2) SPAN:  Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 5% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 5%, 
25%, 50%, 75% and 100% input signal.  Check that the out-
put signal for the respective input signal remains within 
accuracy described in the data sheet.  When the output is 
out of tolerance, recalibrate the unit according to the “AD-
JUSTMENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

M8AP