CONNECTION DIAGRAM

The M6SVF, by its fast-response feature, 
is not designed to eliminate noise present 
in the input signal.  
Use a shielded twisted-pair cable to prevent 
noise from entering through the input wiring.

+

OUTPUT

5

6

7

8

1

2

+

+

POWER

SIGNAL 

SOURCE

CONNECTOR

POWER

 

WIRING INSTRUCTIONS

  • Applicable wire size

     

Solid:     0.2 to 2.5 mm

2

 (0.55 to 1.75 dia.)

     

Stranded:  0.2 to 2.5 mm

2

 (Tinning wire ends may 

     

 

 

  cause contact failure and therefore is not 

       

 recommended.)

     

 Ferruled:  0.2 to 1.5 mm

2

 (0.55 to 1.35 dia.)

  • Expose wire conductors by 8 mm (0.31”).

Expose 8 mm

• 

How to Connect Wires

Screwdriver

Wire

1) Insert a minus screwdriver into the wire entry opening, 

between the clamp and the housing, until its tip hits the 

bottom where it is firmly held.

Tension Clamp

Screwdriver

2) Insert a wire.  Push the screwdriver toward the direction 

indicated with the arrow in the figure below to widen the 

opening if necessary.

Wire Entry

Wire

3) Confirm that the wire tip hits the bottom and pull out the 

screwdriver in holding it in position.

  Confirm that the wire’s insulation tube is not caught in 

the clamp.