background image

MODEL: M5VS

Super-mini Terminal Block Signal Conditioners M5-UNIT

SIGNAL TRANSMITTER

Functions & Features
• Converts a DC input into an isolated DC signal
• High-density mounting
• Power LED
• CE marking for 24 V power

25 (.98)

97

(3.82)

41 (1.61)

mm (inch)

MODEL: M5VS-[1][2]-[3][4]

ORDERING INFORMATION

Specify a code from below for each [1] through [4].
• Code number: M5VS-[1][2]-[3][4]
  (e.g. M5VS-4W4W-R/K/Q)
Specify variables.
• Special input and output ranges (For codes Z & 0)
• Specify the specification for option code /Q
  (e.g. /C01 /V01)

[1] INPUT

Current

A: 4 – 20 mA DC (Input resistance 249 Ω)
A1: 4 – 20 mA DC (Input resistance 49.9 Ω)
B: 2 – 10 mA DC (Input resistance 499 Ω)
C: 1 – 5 mA DC (Input resistance 1000 Ω)
D: 0 – 20 mA DC (Input resistance 49.9 Ω)
E: 0 – 16 mA DC (Input resistance 61.9 Ω)
F: 0 – 10 mA DC (Input resistance 100 Ω)
G: 0 – 1 mA DC (Input resistance 1000 Ω)
H: 10 – 50 mA DC (Input resistance 20 Ω)
Z: Specify current (See INPUT SPECIFICATIONS)

Voltage

3: 0 – 1 V DC (Input resistance 1 MΩ min.)
4: 0 – 10 V DC (Input resistance 1 MΩ min.)
5: 0 – 5 V DC (Input resistance 1 MΩ min.)
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
4W: -10 – +10 V DC (Input resistance 1 MΩ min.)
5W: -5 – +5 V DC (Input resistance 1 MΩ min.)
0: Specify voltage (See INPUT SPECIFICATIONS)
(CE not available)

01: Specify voltage (See INPUT SPECIFICATIONS)
(Choose 01 for CE. Power suffix code R only.)
02: Specify voltage (See INPUT SPECIFICATIONS)
(CE not available)

[2] OUTPUT

Current

A: 4 – 20 mA DC (Load resistance 550 Ω max.)
D: 0 – 20 mA DC (Load resistance 550 Ω max.)
Z: Specify current (See OUTPUT SPECIFICATIONS)

Voltage

1: 0 – 10 mV DC (Load resistance 100 kΩ min.)
(CE not available)
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)
(CE not available)
3: 0 – 1 V DC (Load resistance 100 Ω min.)
4: 0 – 10 V DC (Load resistance 1000 Ω min.)
5: 0 – 5 V DC (Load resistance 500 Ω min.)
6: 1 – 5 V DC (Load resistance 500 Ω min.)
1W: -10 – +10 mV DC (Load resistance 100 kΩ min.)
(CE not available)
2W: -100 – +100 mV DC (Load resistance 100 kΩ min.)
(CE not available)
3W: -1 – +1 V DC (Load resistance 800 Ω min.)
4W: -10 – +10 V DC (Load resistance 8000 Ω min.)
5W: -5 – +5 V DC (Load resistance 4000 Ω min.)
0: Specify voltage (See OUTPUT SPECIFICATIONS)
01: Specify voltage (See OUTPUT SPECIFICATIONS)
(CE not available)

[3] POWER INPUT

AC Power

M: 85 – 264 V AC (Operational voltage range 85 – 264 V,
47 –66 Hz)
(CE not available)

DC Power

R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[4] OPTIONS (multiple selections)

Response Time (0 – 90 %)

blank: Standard (≤ 0.5 sec.)
/K: Fast Response (Approx. 25 msec.)
/F: Fast Response (≤ 1 msec.)

Other Options

blank: none
/Q: Option other than the above (specify the specification)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for M5VS Series

Page 1: ...ECIFICATIONS Choose 01 for CE Power suffix code R only 02 Specify voltage See INPUT SPECIFICATIONS CE not available 2 OUTPUT Current A 4 20 mA DC Load resistance 550 Ω max D 0 20 mA DC Load resistance 550 Ω max Z Specify current See OUTPUT SPECIFICATIONS Voltage 1 0 10 mV DC Load resistance 100 kΩ min CE not available 2 0 100 mV DC Load resistance 100 kΩ min CE not available 3 0 1 V DC Load resist...

Page 2: ...mum span 1 mA Offset Max 1 5 times span Load resistance Output drive 11 V max DC Voltage Output code 0 CE Voltage range 10 10 V DC Minimum span 1 V Offset Max 1 5 times span Load resistance Output drive 10 mA max at 1 V Max 1 25 mA output drive for negative voltage Output code 01 Not CE Voltage range 1 1 V DC Minimum span 10 mV Offset Max 1 5 times span Load resistance Min 100 kΩ Min 1 MΩ for nega...

Page 3: ... 4 1 39 1 2 3 4 5 6 7 8 SCHEMATIC CIRCUITRY CONNECTION DIAGRAM Isolation S Z Low Drift Amplifier Output Driver INPUT 3 4 1 2 Input shunt resistor incorporated for current input OUTPUT 5 6 8 7 U V POWER POWER LED Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und...

Page 4: ...ature must be within 5 to 55 C 23 to 131 F with relative humidity within 0 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables power supply input and output close to noise sources relay drive cable high frequency line etc Do not bind these cables together with those in which noises are present Do not install them in the same duct Install lightning surge protec...

Page 5: ... units DIN RAIL 35mm wide 8 M3 5 SCREW 7 3 29 1 2 3 4 5 6 7 8 OUTPUT 5 6 7 8 INPUT 3 4 U V POWER CHECKING 1 Terminal wiring Check that all cables are correctly con nected according to the connection diagram 2 Power input voltage Check voltage across the terminal 7 8 with a multimeter 3 Input Check that the input signal is within 0 100 of the full scale 4 Output Check that the load resistance meets...

Reviews: