background image

M5DY

EM-2476 Rev.

9

  P. 2 / 2

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the 
connection diagram on the front of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

94 (3.70)

3 (.12)

25 (.98)

41 (1.61)

[3.3 (.13)]

• When mounting, no extra space is needed between units.

DIN RAIL

35mm wide

8–M3.5 SCREW

7.3 (.29)

1 2

3 4

5 6

7 8

 

CONNECTION DIAGRAM

+

OUTPUT

5

6

+

+

1

2

3

4

2-WIRE

TRANSMITTER

+

MONITOR

(1 – 5V DC)

V

8

7

U(+)

V(–)

POWER

2-WIRE

XMTR

+

+

INPUT

+

+

1

4

2

+

+

250Ω

■ 

When Used as DC Supply

■ 

When Used as Isolator

3

1

4

2

250Ω

3

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal

7 – 8 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for
more than 10 minutes.

1) ZERO:  Apply 0% input and adjust output to 0%.
2) SPAN:  Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%,
50%, 75% and 100% input signal.  Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for
protection against induced lightning surges.  Please contact
M-System to choose appropriate models.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Reviews: