M3LPA

P.  / 9

EM-2656 Rev.4

FREQUENCY TRANSMITTER

(field- and PC-configurable)

MODEL

M3LPA

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If  you  have  any  problems  or  questions  with  the  product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Signal conditioner ......................................................... (1)
  I/O range and tag name label sheet ............................ (1)

 MODEL NO.

Confirm  Model  No.  marking  on  the  product  to  be  exactly 
what you ordered.

 INSTRUCTION MANUAL

This  manual  describes  necessary  points  of  caution  when 
you use this product, including installation, connection and 
basic maintenance procedures.
The M3LPA with Option /A is programmable using the PC 
configurator software.  For detailed information on the PC 
configuration, refer to the M3CON instruction manual.  The 
M3CON PC Configurator Software is downloadable at M-
System’s web site: http://www.m-system.co.jp.

POINTS OF CAUTION

 CONFORMITY WITH UL

• This equipment is suitable for use in a Pollution Degree 2 

environment.

• This equipment is to be used with the maximum operat-

ing voltage 30Vrms and 42.4Vpeak or 60V DC.

• The equipment must be mounted inside a suitable fire en-

closure.

• Operating temperature: -25 to +55°C (-13 to +131°F)

 CONFORMITY WITH EC DIRECTIVES

• Functional  insulation  is  maintained  between  the  signal 

input and output.  The input voltage must not exceed 70V 
to maintain the CE conformity.

• Altitude up to 2000 meters
• The equipment must be mounted inside a panel.
• Insert noise filters for the power source connected to the 

unit.  Densei-Lambda Model MBS-1220-22 or equivalent 
is recommended.

• The actual installation environments such as panel con-

figurations,  connected  devices,  connected  wires,  may  af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 5 – 8VA
  10 – 32V DC rating: 9 – 36V, approx. 3W

 SAFETY PRECAUTION

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

 ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air, 

install the unit inside proper housing with sufficient ven-
tilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -25 to +65°C     

(-13 to +149°F) with relative humidity within 0 to 95% RH 
in order to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with ca-

bles, etc.

 WIRING

• Do  not  install  cables  (power  supply,  input  and  output) 

close  to  noise  sources  (relay  drive  cable,  high  frequency 
line, etc.).

• Do  not  bind  these  cables  together  with  those  in  which 

noises are present.  Do not install them in the same duct.

 AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying  complete  performance  described  in  the  data 
sheet.

Summary of Contents for M3LPA

Page 1: ...e filters for the power source connected to the unit Densei Lambda Model MBS 1220 22 or equivalent is recommended The actual installation environments such as panel con figurations connected devices c...

Page 2: ...ng body pull up the driver and pull out the terminal block INSTALLATION DIN RAIL MOUNTING Set the unit so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of the uni...

Page 3: ...power and DC power connect to different terminals 2 DC POWER INPUT 1 U V 1 3 2 6 5 4 CONFIGURATOR JACK 7 8 10 12 OUTPUT AC POWERED TYPE 2 AC POWER WIRING INSTRUCTIONS Applicable wire size Solid 0 2 to...

Page 4: ...e selected with the DIP SW4 1 through SW4 3 See Tables 9 and 10 For detailed information on the PC configuration refer to the M3CON instruction manual EXTERNAL INTERNAL VIEWS CONFIGURATION MODE DIP SW...

Page 5: ...LD1 green light is blink ing 2 Threshold Calibration Mode Press MODE button for longer than 5 seconds until the LD1 red light is ON 3 Threshold Setting Apply the full scale input level e g 100 Hz from...

Page 6: ...WN UP MODE PUSH DOWN PUSH UP When you set 0 or 100 input output ranges keep pressing UP or DOWN button until the LD1 flashes for approx 5 seconds and turns off which indicates the setup is complete Wh...

Page 7: ...itter is installed and operational fine zero and span tuning can be performed as explained below Both zero and span are adjustable within 15 1 Run Mode Confirm that the LD1 green light is blink ing 2...

Page 8: ...nto voltage V e g Offset 10mA 10mA x 1 10 1V Table 14 PULSE AMPLITUDE SENSITIVITY SCALE 50 100V p p 1 20 25 50V p p 1 10 10 25V p p 1 5 5 10V p p 1 2 1 5V p p 1 0 5 1V p p 1 0 1 0 5V p p 1 A specific...

Page 9: ...g the date that such product was originally purchased if such product has been used under normal operating conditions and properly maintained M System s sole liability and purchaser s exclusive remedi...

Reviews: