MODEL: M2PA

Isolation: Input to output to power
Input waveform
  Average sensing: Sine wave
Overrange output: 0 to 120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)

INPUT SPECIFICATIONS

Frequency: 50 or 60 Hz
Input burden: 0.5 VA max.
Overload capacity: 200 % of rating for 1 minute, 120 %
continuous
Operational range: 0 – 120 % of rating

OUTPUT SPECIFICATIONS

• DC Current: 0 – 20 mA DC
Minimum span: 1 mA
Offset: Max. 1.5 times span
Load resistance: Output drive 15 V max.
• DC Voltage: 0 – 12 V DC
Minimum span: 5 mV
Offset: Max. 1.5 times span
Load resistance: Output drive 1 mA max.; at ≥ 0.5 V

INSTALLATION

Power Consumption
•AC Power input:
 Approx. 3 VA at 100 V
 Approx. 4 VA at 200 V
 Approx. 5 VA at 264 V
•DC Power input: Approx. 3 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lbs)

PERFORMANCE in percentage of span

Accuracy: ±0.4 %
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Ripple: 0.5 %p-p max. (100/120 Hz)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output
to power to ground)

STANDARDS & APPROVALS

CE conformity:
  EMC Directive (2004/108/EC)
  EN 61000-6-4 (EMI)

  EN 61000-6-2 (EMS)
  Low Voltage Directive (2006/95/EC)
  EN 61010-1
  Installation Category II
  Pollution Degree 2
  Max. operating voltage 300 V
  Input or output to power: Reinforced insulation
  Input to output: Basic insulation
Approval:
  UL/C-UL nonincendive Class I, Division 2,
  Groups A, B, C, and D hazardous locations
  (UL 1604, CAN/CSA-C22.2 No.213)
  UL/C-UL general safety requirements
  (UL 61010B-1, CAN/CSA-C22.2 No.1010-1)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG