SIGNAL TRANSMITTER
(PC programmable)
MODEL
M2EXV
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■
PACKAGE INCLUDES:
Signal conditioner (body + base socket) .............................(1)
■
MODEL NO.
Confirm Model No. marking on the side of the product to be
exactly what you ordered.
■
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
detailed operation regarding settings. For detailed explana-
tions, please refer to the Model M2EXV operating manual
(EM-5133-B).
The M2EXV is programmable using a PC. For detailed in-
formation on the PC configuration, refer to the M2ECFG
users manual (EM-5147).
The M2ECFG Configurator Software and the operating
manual (EM-5133-B) are downloadable at M-System’s web
site: http://www.m-system.co.jp
POINTS OF CAUTION
■
CONFORMITY WITH EU DIRECTIVES
•
This equipment is suitable for Pollution Degree 2 and In-
stallation Category II. Reinforced insulation (signal in-
put or output to power input: 300V) and basic insulation
(signal input to output: 300V) are maintained. Prior to
installation, check that the insulation class of this unit
satisfies the system requirements.
•
Altitude up to 2000 meters.
•
The equipment must be mounted inside a panel.
•
The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
•
The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
•
Install lightning surge protectors for those wires connect-
ed to remote locations.
■
POWER INPUT RATING & OPERATIONAL RANGE
Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V, 47 – 66 Hz,
≤ 4.5VA at 100V AC
≤ 6.5VA at 200V AC
≤ 8.5VA at 264V AC
24V DC rating: 24V ±10%, ≤ 2.3W
110V DC rating: 85 – 150V, ≤ 2.3W
■
GENERAL PRECAUTIONS
Before you remove the unit from the socket or mount it,
turn off the power supply and input signal for safety.
■
ENVIRONMENT
•
Indoor use
•
When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
•
Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•
Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 10 to 85% RH
in order to ensure adequate life span and operation.
■
WIRING
•
Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•
Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■
AND ....
•
The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
•
With voltage output, do not leave the output terminals
shortcircuited for a long time. The unit is designed to en-
dure it without breakdown, however, it may shorten ap-
propriate life duration.
•
The edge of the display may be hidden by the frame and
invisible depending on the view angle.
COMPONENT IDENTIFICATION
Connection Diagram
(Side)
Body
Base Socket
Display
Fixing Screw
(screw for attaching
the body to the socket)
Mode
Set
Up
Down
Specification