background image

M2EXV

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

EM-5133-A Rev.1  P. 1 / 4

SIGNAL TRANSMITTER

(PC programmable)

MODEL

M2EXV

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner (body + base socket) .............................(1)

 

MODEL NO.

Confirm Model No. marking on the side of the product to be 
exactly what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
detailed operation regarding settings.  For detailed explana-
tions, please refer to the Model M2EXV operating manual 
(EM-5133-B).
The M2EXV is programmable using a PC.  For detailed in-
formation on the PC configuration, refer to the M2ECFG 
users manual (EM-5147).  
The M2ECFG Configurator Software and the operating 
manual (EM-5133-B) are downloadable at M-System’s web 
site: http://www.m-system.co.jp

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• 

This equipment is suitable for Pollution Degree 2 and  In-
stallation Category II.  Reinforced insulation (signal in-
put or output to power input: 300V) and basic insulation 
(signal input to output: 300V) are maintained.  Prior to 
installation, check that the insulation class of this unit 
satisfies the system requirements.

• 

Altitude up to 2000 meters.

• 

The equipment must be mounted inside a panel.

• 

The equipment must be installed such that appropriate 
clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• 

The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

• 

Install lightning surge protectors for those wires connect-
ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

Locate the power input rating marked on the product and 
confirm its operational range as indicated below:
  100 – 240V AC rating: 85 – 264V, 47 – 66 Hz,
     

≤ 4.5VA at 100V AC

     

≤ 6.5VA at 200V AC

     

≤ 8.5VA at 264V AC

  24V DC rating: 24V ±10%, ≤ 2.3W
  110V DC rating: 85 – 150V, ≤ 2.3W

 

GENERAL PRECAUTIONS

Before you remove the unit from the socket or mount it, 
turn off the power supply and input signal for safety.

 

ENVIRONMENT

• 

Indoor use

• 

When heavy dust or metal particles are present in the 
air, install the unit inside proper housing with sufficient 
ventilation.

• 

Do not install the unit where it is subjected to continuous 
vibration.  Do not subject the unit to physical impact.

• 

Environmental temperature must be within -5 to +55°C     
(23 to 131°F) with relative humidity within 10 to 85% RH 
in order to ensure adequate life span and operation.

 

WIRING

• 

Do not install cables close to noise sources (relay drive 
cable, high frequency line, etc.).

• 

Do not bind these cables together with those in which 
noises are present.  Do not install them in the same duct.

 

AND ....

• 

The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

• 

With voltage output, do not leave the output terminals 
shortcircuited for a long time. The unit is designed to en-
dure it without breakdown, however, it may shorten ap-
propriate life duration.

• 

The edge of the display may be hidden by the frame and 
invisible depending on the view angle.

COMPONENT IDENTIFICATION

Connection Diagram

(Side)

Body

Base Socket

Display

Fixing Screw

(screw for attaching 
the body to the socket)

Mode

Set

Up

Down

Specification

Summary of Contents for M2EXM

Page 1: ...urations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity Install lightning surge protectors for those wires connect ed to remote locations POWER INPUT RATING OPERATIONAL RANGE Loc...

Page 2: ...OUNTING Set the base socket so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of base socket on the DIN rail and push in the lower When removing the socket push down the DIN rail adaptor utilizing a minus screwdriver and pull WALL MOUNTING Refer to the drawings in the shown below TERMINAL CONNECTIONS Connect the unit as in the diagram below or refer to the conn...

Page 3: ...to shift through setting parameter and to increase or select setting value Down button Used to shift through setting parameter and to decrease or select setting value Configurator Jack Used to configure with M2E configurator software model M2ECFG At the same time set the lock out setting of the unit to lock DIP SWITCH The internal DIP switch for output setting is required to select output types be...

Page 4: ...ay value is correct but the output is out of accuracy perform the output fine adjustment Refer to this manual when adjusting with front buttons Refer to the M2ECFG users manual EM 5147 when adjusting with M2E Configurator Software model M2ECFG And then follow the procedure shown below INPUT FINE ADJUSTMENT 1 Set the input signal to 0 and adjust the input display to 0 by 69 Input Zero fine adjust 2...

Reviews: