8.

 

Fuse (Image 3, Pos. 1) 
 
If the adapter is not working after connecting it to mains, please check out first if the 
plug socket of mains is energized (230VAC, 50Hz). If mains is OK, the fuse inside the 
adapter could be blown. 

Changing of the fuse is only allowed for skilled electric personnel!  

To control the fuse and possibly change it (factory-made data: 0,4A slow blow 
5x20mm fuse) unplug the adapter from mains and unplug any switch-off unit from 
the plug socket (Image 1, Pos. 2). After removal of 4 screws and the top side of the 
housing you will see the fuse holder (Image 3, Pos. 1). The cover of the fuse holder 
needs to be removed upwards carefully. The fuse will be taken out of the holder 
carefully, be checked and replaced eventually. After that, the cover of the fuse holder 
will be reinstalled. 
 

Attention: Replace the fuse by same typ and electric parameters! 

Upon request the adapter can be delivered with different fuse parameters which are 
corresponding to the load (switch-off unit).  
After the fuse change, both parts of the housing are joint together and fixed by the 
screws again. Make sure you are not violating the cables by bending or constrict 
them. 
If the fuse is not blown and there is furthermore no function, you need to return the 
adapter to the manufacturer. 
 
 

 

Image 3: Adapter inside view with position of the fuse (1)

 

Summary of Contents for LiBo-8

Page 1: ...ortant notice from the Manufacturer Article No 25630009 01 for 8 und 25630010 01 for 16 Image 1 LiBo Adapter with Toroid Coil 8 5 Housing with plug socket 2 Mains Control Lamp 1 Duo LED Red Green 4 Cover Caps 3 red Push button Test 6 green Push button Reset 7 Image 2 Mains plug 8 ...

Page 2: ...apter 6 from this manual If there is a loss of mains power and mains comes back the LED Image 1 Pos 4 will be red for a short period of time Mains control lamp Image 1 Pos 1 is off and finally change to the status prior to mains loss Alarm Red or normal operation Green If the mains control lamp Image 1 Pos 1 is on the plug socket Image 1 Pos 2 is energized 2 Duo LED Red Green Image 1 Pos 4 This LE...

Page 3: ... if the red LED will not shine green after reset see chapter 5 there will be a fault in the sensor s circuitry or the voltage created by the disturbance is outside the calibration range In this case you press simultaneously the Test push button Image 1 Pos 6 and the Reset push button Image 1 Pos 7 for 2 4 seconds The circuitry automatically adjusts itself to the new voltage After that a self test ...

Page 4: ...r Image 3 Pos 1 The cover of the fuse holder needs to be removed upwards carefully The fuse will be taken out of the holder carefully be checked and replaced eventually After that the cover of the fuse holder will be reinstalled Attention Replace the fuse by same typ and electric parameters Upon request the adapter can be delivered with different fuse parameters which are corresponding to the load...

Page 5: ...cm Direct current of the cable to be monitored Toroid coil 8 minimum of 50A Toroid coil 16 minimum of 100A higher currents upon request Plug socket output for loads mains switched to plug socket by DPST relay Protection Earth PE of plug connected to PE of plug socket Factory made fuse 5x20mm 0 4A slow blow inside the housing Attention please read carefully chapter 8 for safety advices Galvanic iso...

Page 6: ...s Caused by a variety of disturbances on DC cables a calibration might not be successful for a proper operation of the adapter Before placing an order the manufacturer presumes the test of an adapter on loan and for a certain amount of time to make sure the adapter is working properly in the application of the customer Warranty corresponding to the General Terms and Conditions of the manufacturer ...

Page 7: ...7 Der Partner in Sachen Elektronik Königsberger Str 8 85368 Moosburg Tel 0 87 61 72 54 0 Fax 0 87 61 72 54 27 Email info m system gmbh de www m system gmbh de Moosburg October 7th 2019 ...

Reviews: