LC / LCS
P. 2 / 4
EM-1355 Rev.3
DISPLAY SETTING PROCEDURE
Option /E2
Normal Operating
Mode
Display Configuration
Mode
ITEM : ‘CFG’
Select engineering
unit
ITEM : ‘UNIT’
NEXT
NEXT
NEXT
ENTER
Press NEXT one
or more times.
ENTER
Select decimal point
position
ITEM : ‘DOT P’
NEXT
Press NEXT one
or more times.
ENTER
Calibration Mode
Adjust the display 0% &
100% values
ITEM : ‘CAL’
Set the present input value as 0%.
Display shows AD conversion value
*
1
.
ITEM : ‘ADJ Z’
NEXT
ENTER
Press NEXT to read and show
the present input value
(AD conversion value)
Press NEXT to read and show
the present input value
(AD conversion value)
ENTER
Set the present input value as 100%.
Display shows AD conversion value
*
1
.
ITEM : ‘ADJ S’
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
Select 0%
scaling value
ITEM : ‘SCL Z’
NEXT
Numeric Input
Mode
Exit
ENTER
Select 100%
scaling value
ITEM : ‘SCL S’
Numeric Input
Mode
Exit
ENTER
NEXT
NEXT
NEXT
Display Initialization
Mode
ITEM : ‘INIT’
ITEM : ‘NO’
Exit Numeric
Input Mode
NEXT
ENTER
Press ENTER to reset
the display
configuration to the
initial state.
ITEM : ‘YES’
Press NEXT to
choose among
‘0’ –> ‘1’ –> ‘-0’ –>
‘-1’ –> ‘0’ ....
Most Significant Digit
(upper line)
Press NEXT to
choose among ‘0’
through ‘9.’
Press ENTER to
move to the next
LS digit.
Less Significant Digits
(upper line)
NEXT
NEXT
The range is set to
10000 or -10000
and the numeric
input mode ends.
Select ‘1’ or ‘-1’
Select
‘0’ or ‘-0’
Numeric Input Mode
Press ENTER key in maintaining NEXT key
pressed to return to Normal Operating Mode
from any setting mode.
Select among %,
µ
V, mV, V, mA,
°
C,
°
F,
Ω
, DEG K, mHz, Hz, kHz,
VAC, AAC, mg, g, kg, t, rpm and rps.
Apply the input signal for 0%.
Apply the input signal for 100%.
(Value Set)
(Value Set)
‘AD conversion value’ means the internal digital data representing
the input signal, which is computed to a percentage.
It is not a % or engineering unit value.
*
1.
Value
Unit, Item
ENTER Key
NEXT Key
Backlight : Green (normal)
Red (simulated output)