background image

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 14 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Alarm operations:  Check the alarm operations referring 

to the figure below.

5) Output load:  Check that the output load is 380V 

AC/120VA or 125V DC/30W at the maximum (≤ 0.5A).  

For maximum relay life with inductive load, external pro-

tection is recommended.

Alarm Trip Operation  

Terminal No. in parentheses

Trip Operation in Power Failure

: Terminals 1 – 2, 9 – 10 turn ON.

0

50

100

Input
(%)

Lo Setpoint

Hi Setpoint

Hi Output

(9–15)ON

Lo Output

(1–2)ON

(1–11)ON

(9–10)ON

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.

• Hi Setpoint

   Increase the input signal from a value lower than the set-

point and check that the trip point remains within the 
accuracy described in the data sheet.

• Lo Setpoint

   Decrease the input signal from a value higher than the 

setpoint and check that the trip point remains within the 
accuracy described in the data sheet.

When the setpoints are shifted, please contact M-System’s 
Sales Office or representatives.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

KSL2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN