JPSM
EM-1689 Rev.5
P. 6 / 8
■
COUNT COMPENSATION
The pulse waveform status at the moment of power turned ON may cause the counter error by 1 count. Proceed according to
the following flow chart for compensating this error.
Count Compensation
Compensation Complete
Compensation Complete
Pulse status at the moment
of power supplied?
Voltage Pulse
Dry Contact
: High
: OFF
Voltage Pulse
Dry Contact
: Low
: ON
Turn the front DIP SW (SW2-4 or 1-4
*
) ON or OFF
respectively so that the Input Monitor LED (PL1 or
PL2
*
) is turned OFF.
The transmitter counts the first pulse sinking after its
rising since the power is turned on.
For voltage pulse, the first count is made when
waveform shifts from High to Low status, while for a
dry contact, it is made when the wave shifts from
OFF to ON.
Turn the front DIP SW (SW2-4 or 1-4
*
) ON or OFF
respectively so that the Input Monitor LED (PL1 or
PL2
*
) is turned ON.
The transmitter counts the first pulse rising after its
sinking since the power is turned on.
For voltage pulse, the first count is made when
waveform shifts from Low to High status, while for a
dry contact, it is made when the wave shifts from
ON to OFF.
Power ON
Hi or OFF
Lo or ON
Hi or OFF
Lo or ON
Counts
Power ON
Counts
1
2
1
2
*
SW2 and PL1 are for Input 1, SW1 and PL2 are for Input 2.