SOFTWARE SETTING
Please refer to the Operation Manual for Model PU-2x (EM-9255), Section B: (B-1) Introduction, (B-2) General Operation
Description, (B-3) Operation Flowchart for general information.
[GROUP 01]
ITEM MDFY. DATA INPUT
DISPLAY
DEFAULT CONTENTS
01
S
N/A
MAINTENANCE SWITCH
0
MTSW : MON.MODE
0: Data indication only.
1
MTSW : PRG.MODE
1: All ‘P’ marked parameters are modifiable.
02
P
Alphabets & No TG : XXXXXXXXXX
N/A
Tag name entry (10 characters max.)
03
P
Percentage
OUTPER XXX.XX
N/A
Output monitor (%) & simulation output
05
D
No input
INPPER XXX.XX
N/A
Input monitor (%)
06
P
No input
CNT XXXXXXXXX
N/A
Input count monitor; or setting to a specific count value
07
D
No input
N/A
Input specification selected with the front rotary switch
SW : IN_V 1/20
SW = 0, Voltage pulse input, Sensitivity scale = 1/20
SW : IN_V 1/10
SW = 1, Voltage pulse input, Sensitivity scale = 1/10
SW : IN_V 1/5
SW = 2, Voltage pulse input, Sensitivity scale = 1/5
SW : IN_V 1/2
SW = 3, Voltage pulse input, Sensitivity scale = 1/2
SW : IN_V 1/1
SW = 4, Voltage pulse input, Sensitivity scale = 1/1
SW : IN_V 5/1
SW = 5, Voltage pulse input, Sensitivity scale = 5/1
SW : IN_V 10/1
SW = 6, Voltage pulse input, Sensitivity scale = 10/1
SW : IN_OC, mA
SW = 7, Open collector, mechanical contact or two-wire cur-
rent pulse input
SW : no use
SW = 8, (not used)
SW : no use
SW = 9, (not used)
08
P
0
Input count at power off
0
COUNT UNKEEP
Not held (Cold Start)
1
COUNT KEEP
Held (Hot Start)
10
P
0
Linearization
0
STRAIGHT
Without
1
CURVED
With (ITEM 60 to 91 for segment data input)
11
P
0
Count mode
0
UP_EDGE
Count at pulse rise
1
DOWN_EDGE
Count at pulse sink
2
UPDOWN_EDGE
Count at both pulse rise and sink
12
P
0
Count overflow mode
0
115%_HOLD
Hold at 115%
1
100%_HOLD
Hold at 100%
2
100%_RESET
Reset at 100%
14
P
Numeric
LO XXXXXXXXX
0
Input zero count (0% input) (0 to 99999999)
15
P
Numeric
HI XXXXXXXXX
1000
Input span count (100% input) (0 to 99999999)
19
P
Percentage
FINZER XXX.XX
0.00
Fine zero adjustment
OUTPER XXX.XX
When data is entered, output (%) is shown.
20
P
Percentage
FINSPN XXX.XX
100.00
Fine span adjustment
OUTPER XXX.XX
When data is entered, output (%) is shown.
21
P
1
Alarm mode
0
NO ALARM
No alarm trip
1
UPPER ALARM
High alarm trip
22
P
Percentage
ALARM XXX.XX
100.00
Alarm setpoint (-15.00 to +115.00%)
24
P
Seconds
ALTIME XXXX.X
3.0
Alarm delay at the startup (2.0 to 1000.0 seconds)
60
61
:
:
:
90
91
P
P
:
:
:
P
P
Percentage
Percentage
:
:
:
Percentage
Percentage
X (01) : XXX.XX
Y (01) : XXX.XX
:
:
:
X (16) : XXX.XX
Y (16) : XXX.XX
0.00
0.00
0.00
0.00
Linearization table (16 points)
Set at the maximum of 16 pairs of input (X) and output (Y)
calibration points in %. Fill data from the lowest ITEM
No. from the lowest calibration point and add as many as
required. The output in the undefined range is maintained
at the value of the first and the last calibration points.
Modification Code
D: No modification (writing) possible. Used only for monitoring (reading).
S: Modifiable at any time.
P: Modifiable only when the MAINTENANCE SWITCH is in the “PRG” mode.