JB2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-2642 Rev.3 P. 3 / 5
FRONT VIEW & PROGRAMMING
Please refer to the Operation Manual for Model PU-2x (EM-9255), Section A: (A-1) Introduction, (A-2) General Operation
Description, (A-3) General Operation Flow Chart for general information.
Front Cover (open)
Span Adj.
Zero Adj.
RUN Output LED
MAN. Status LED
UP Command LED
DOWN Command LED
MAN. Command LED
Modular Jack
• PROGRAMMING WITH PU-2x
G
ITEM No.
I
(
)
D
Response Messages
GROUP No.
Data to be entered
or Messages
LCD Display
• Response Messages
OK: OK
NG: No good. Check modular jack connection.
ER: Communication error
[GROUP 01]
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
01
S
MAINTENANCE SWITCH
0
MTSW : MON.MODE
0: Data indication only.
1
MTSW : PRG.MODE
1: All ‘P’ marked parameters are modifiable. *
1
02
P
Alphabets & No.
TG : XXXXXXXXXX
Tag name entry (10 characters max.)
03
D
No input
OUTPER : XXX.XX
Output in %
04
D
No input
OUTVAL : XX.XXX
Output value in mA
05
D
No input
INPPER : XXX.XX
Input in %
06
D
No input
INPVAL : XX.XXX
Input value in mA
10
P
WRITE DEFAULT
Initializing all setting values to the factory standard ones.
ENTR
COMPLETED
Initialization complete
21
P
Manual control mode (factory set value: 1)
Specifies the initial MV output value when starting MAN control
1
1 : DIRECT
CAS control signal value
2
2 : TRACE BACK
CAS control signal value going back for ITEM 28 set time period
3
3 : FIXED VALUE
Fixed value set in ITEM 29
22
P
Numeric
SLDBAK : XXX.XX
MAN/CAS transition response (%/second)
Selectable range: 0.00 to 200.00
No sliding-back function with 0.00
23
P
UP/DOWN response mode (factory set value: 0)
0
0 : UNIFORM
Constant ramp rate while the key is held down.
1
1 : ONE+UNIFORM
Normal response rate for once when the key is pressed.
Constant ramp rate if it is continuously held down.
2
2 : ACCELERATED
Accelerated response when the key is pressed until it reaches the
constant ramp rate.
24
P
Numeric
KEYRES : XXX.XX
UP/DOWN response time (ramp rate) (%/second)
Selectable range: 0.00 to 200.00 (factory set value: 10.00)
25
P
High/Low alarm mode at CAS control (factory set value: 0)
0
0 : NO ALARM
No alarm trip
1
1 : LOW ALARM
Low alarm trip only
2
2 : HIG ALARM
High alarm trip only
3
3 : ALL ALARM
High/Low alarm trip
26
P
Numeric
ALMLOW : XXX.XX
CAS input Low alarm setpoint (%)
Selectable range: -25.00 to 125.00 (factory set value: -25.00)
27
P
Numeric
ALMHIG : XXX.XX
CAS input High alarm setpoint (%)
Selectable range: -25.00 to 125.00 (factory set value: 125.00)
28
P
Numeric
TRACEBACK : XX.X
Retroactive time period (seconds)
Selectable range: 0.0 to 10.0 (factory set value: 0.0)
29
P
Numeric
MANFIX : XXX.XX
Initial manual control value (%)
Selectable range: -25.00 to 125.00 (factory set value: 0.00)
30
P
Numeric
PWRFIX : XXX.XX
Output in % after power on in manual control mode
Selectable range: -25.00 to 125.00 (factory set value: -25.00)
31
P
Output value after power on
(see “JB2 Actions when the Power Supply is Recovered after Failure.”)
0
0: HOLD VALUE
The value stored at the moment of power failure
1
1: FIXED VALUE
The value preset in the ITEM 30
32
D
No input
NVRWRCNT: XXX
Number of rewriting E
2
PROM (32-bit)
Count when changing program or power off