R7F4DD-DAC16C-C

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8007-E  P. 2 / 8

COMPONENT IDENTIFICATION

I/O Connector

Operation Mode

Setting DIP SW (SW1)

Exc. Supply

Connector

Node Address Setting

Rotary SW

Status Indicator LED

Discrete I/O Status Indicator LED

Communication/Power Supply Terminal Block

Configurator Jack

 

FRONT VIEW

 

SIDE VIEW

CONFIG

×10

×1

SW1

  

ON

MS

NS

0

0

X

Y

1

1

2

2

3

3

4

4

5

5

6

6

7

7

 

STATUS INDICATOR LED

ID

STATUS

COLOR FUNCTION

MS

ON

Green

Normal operation

Blinking

Green

Not set

ON

Red

Critical failure

Blinking

Red

Minor faiure

OFF

No power supply

NS

ON

Green

Connections are established

Blinking

Green

Connections are not established

ON

Red

Critical Link failure

Blinking

Red

Minor Link failure

OFF

No power supply

 

DISCRETE INPUT STATUS INDICATOR LED

LED green indicators shows the signal status.
  ON  : LED ON
  OFF : LED OFF

 

NODE ADDRESS

The left switch determines the tenth place digit, while the
right switch does the ones place digit of the address.
Address is selected between 0 to 63.
(Factory setting: 00) 

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Factory setting : 00

Node Address Setting (x10)

 

OPERATION MODE

(*) Factory default setting

• BAUD RATE (SW1-1, 1-2)

Baud Rate is selected with the rotary switch.

BAUD RATE

SW1

1

2

125 kbps

OFF

OFF

250 kbps

ON

OFF

500 kbps

OFF

ON

Auto-tracking (*)

ON

ON

• STATUS (SW1-3)

Status

SW1

3

Without(*)

OFF

With

ON

• OUTPUT AT THE LOSS OF COMMUNICATION (SW1-4)

Output at the loss of

communication

SW1

4

Hold the output (*)
(maintains the last data 
received normally)

OFF

Reset the output
(turned off)

ON

Note: The R7F4DD communicates in the baud rate setting 

detected at the startup with the switch set to the posi-
tions 0 (125 kbps), 1 (250 kbps) or 2 (500 kbps).  For the 
settings auto-tracking, it analyzes the PLC’ s network 
to determine the baud rate on the network.

Summary of Contents for Devicenet R7F4DD-DAC16C-C

Page 1: ...y have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity GENERAL PRECAUTIONS Before you remove the unit or mount it tur...

Page 2: ...DICATOR LED LED green indicators shows the signal status ON LED ON OFF LED OFF NODE ADDRESS The left switch determines the tenth place digit while the right switch does the ones place digit of the add...

Page 3: ...XC1 Exc supply 1 input 3 NC Unused 4 SNSR EXC2 Exc supply 2 output 5 SNSR EXC2 Exc supply 2 output I O Termianal Assignment Y7 Y6 Y5 Y4 Y3 Y2 Y1 Y0 X7 X6 X5 X4 X3 X2 X1 X0 GND 24V GND 24V Unit side co...

Page 4: ...ve the upper hook of the unit from the DIN rail A C B SURFACE MOUNTING 1 Insert the two DIN rail mounter sliders until it clicks once as shown below A A 2 Mount the unit with M4 screws referring to th...

Page 5: ...84 138 5 43 50 1 97 5 20 3 12 DIN rail 35mm wide 4 16 2 4 3 17 dia 4 16 deep CONNECTION DIAGRAM Y0 GND 24V 2 1 3 Y7 GND 24V 2 1 3 SNSR EXC1 SNSR EXC1 1 2 Exc supply 1 IN SNSR EXC1 SNSR EXC1 1 2 Exc s...

Page 6: ...model R7CFG Refer to the users manual of the software for detailed operations INTERFACE SETTING PARAMETER SETTING RANGE DEFAULT SETTING Communication Timeout 0 32767 0 1 sec 10 0 1 sec DATA ALLOCATIO...

Page 7: ...3 Input 7 Unused Unused 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 15 Output 0 Output 1 Output 2 Output 3 Output 7 Unused Unused 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON S...

Page 8: ...OUTPUT DATA 1 R7F4DD to master INPUT DATA 2 master to R7F4DD R7F4DD DAC16C 1 1 STATUS Status signal can be included in the transmission data when the SW1 3 is ON For details refer to STATUS in I O DA...