CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Alarm operations:  Check the alarm operations referring 

to the figure below.

5) Output load:  Check that the output load is 380 V AC/120 

VA or 125 V DC/30 W at the maximum.  For maximum 

relay life with inductive load, external protection is rec-

ommended.

ALARM RELAY OPERATIONS

–50

0

+50

Deviation
(%)

Output 2

Setpoint

Output 1

Setpoint

Output 1

(9–10)ON

Output 2

(1–2)ON

(1–3)ON

(9–11)ON

Trip Operation in Power Failure

• 

Output 1

:  (9 – 10) turn ON with code 1

     

 

 

(9 – 11) turn ON with code 2

• 

Output 2

:  (1 – 2) turn ON with code 1

     

 

 

(1 – 3) turn ON with code 2

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.

• 

Hi Setpoint

   Increase the input signal from a value lower than the set-

point and check that the trip point remains within the 
accuracy described in the data sheet.

• 

Lo Setpoint

   Decrease the input signal from a value higher than the 

setpoint and check that the trip point remains within the 
accuracy described in the data sheet.

When the trip points are out of tolerance, contact M-Sys-
tem’s Sales Office or local representatives.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.