background image

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Alarm operations:  Check the alarm operations referring 

to the figure below.

5) Output load:  Check that the output load is 380V 

AC/120VA or 125V DC/30W at the maximum.  For maxi-

mum relay life with inductive load, external protection is 

recommended.

Alarm Trip Operation

Terminal No. in parentheses

Trip Operation in Power Failure

Output Code 2

: both relays turn OFF

Output Code 3

: both relays turn ON

0

50

100

Input
(%)

Lo Setpoint

Hi Setpoint

Hi Output

(1–2)ON

Lo Output

(5–6)ON

0

50

100

Input
(%)

Lo Setpoint

Hi Setpoint

Hi Output

(1–2)ON

Lo Output

(5–6)ON

• Output Code 2

• Output Code 3

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.

• Hi Setpoint

   Increase the input signal from a value lower than the set-

point and check that the trip point remains within the 
accuracy described in the data sheet.

• Lo Setpoint

   Decrease the input signal from a value higher than the 

setpoint and check that the trip point remains within the 
accuracy described in the data sheet.

When the setpoints are shifted, please contact M-System’s 
Sales Office or representatives.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.