CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3) Input: Check voltage across the terminal 5 (+) – 6 (–)
with a multimeter.
4) Excitation: Check voltage (5V ±2%) across the terminal
4 (+) – 6 (–) with a multimeter.
5) Relay operation: Check that the relays operates accord-
ing to input signals as shown in the figure below.
6) Output load: Check that the output load is 380V
AC/120VA or 125V DC/30W at the maximum. For use
with inductive load, external protection is recommended.
ALARM TRIP OPERATION
Alarm Trip Operation
Terminal No. in parentheses
Trip Operation in Power Failure
•
Output Code: 1 & 4
•
Output Code: 2 & 3
0
50
100
▲
Input
(%)
Output 2
Setpoint
▲
Output 1
Setpoint
Output 1
(9-10)ON
Output 2
(1-2)ON
(1-3)ON
(9-11)ON
CALIBRATION
This unit is calibrated at the factory with reference input.
Thus, the unit must be calibrated in combination with the
angle sensor that is actually used.
Use a signal source and measuring instruments of sufficient
accuracy level.
■
HOW TO CALIBRATE THE INPUT MONITOR
Connect the unit to the angle sensor and turn the power
supply on, and wait for at least 10 minutes until the unit
warms up before starting calibration.
Adjust output voltage across the input monitor terminal (+)
and the terminal 6 (–).
1) ZERO: Adjust the input angle to 0% and adjust output to
0V. *
1
2) SPAN: Adjust the input angle to 100% and adjust output
to 4V. *
1
3) Check ZERO output again with applying 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
*1. When alarm setpoints cannot be set close to 0% or 100%,
adjust output voltage so as to be slightly higher than 0V
(approx. 0.005V) for ZERO or slightly lower than 4V (ap-
prox. 3.995V) for SPAN.
ADJUSTMENT PROCEDURE
■
ALARM SETPOINT AND DEADBAND (HYSTERESIS)
1) Apply a simulated input signal corresponding to the
alarm setpoint.
2) For a Hi (Lo) setpoint, turn the setpoint adj. from 100%
(0%) until the relay trips.
3) Decrease (increase) the input signal by desired deadband
width.
4) Turn the deadband adj. from 100% (0%) until the relay is
released.
MAINTENANCE
Perform calibration according to the procedures below for
regular maintenance:
■
CALIBRATION OF INPUT MONITOR
1) Warm up the unit for at least 10 minutes.
2) Apply 0%, 25%, 50%, 75% and 100% input angles.
3) Confirm that voltage across the input monitor terminal
(+) and the terminal 6 (–) becomes 0, 1, 2, 3, and 4V cor-
responding to the respective input angles.
4) When the voltage is deviated, recalibrate the unit accord-
ing to the procedure of “CALIBRATION” explained ear-
lier.
■
CALIBRATION OF ALARM OUTPUT
Warm up the unit for at least 10 minutes.
• Hi Setpoint
Increase the input signal from a value lower than the set-
point and check that the trip point remains within the
accuracy described in the data sheet.
• Lo Setpoint
Decrease the input signal from a value higher than the
setpoint and check that the trip point remains within the
accuracy described in the data sheet.
When the trip points are shifted, please contact M-System’s
Sales Office or representatives.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.