WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.6 N·m

CHECKING

Open the unit’s outdoor enclosure cover when you conduct 
checking of the transmitter.  Be sure to close the cover after 
the checking is complete.

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Input:  Check current with an ammeter.  Be sure that the 

connected transmitter allows the load shown in the fol-

lowing table.

MODEL

EQUIVALENT INPUT IMPEDANCE

6BSN-A

230Ω plus output load

6BSN-H

90Ω plus output load × 0.16

3) Output:  Check that output load is within the permissible 

limit shown in the following table.

MODEL

LOAD RESISTANCE

6BSN-A

50 – 350Ω

6BSN-H

50 – 600Ω

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained below.  
Zero and Span adjustments are located behind the top cover 
of the unit.  Open the enclosure cover, release the knurled 
knobs at the front of the unit and open the top cover.
After the calibration is complete, be sure to close both cov-
ers.

1

2

3

4

5

6

VR1

VR2

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the input signal on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 0% input and adjust output to 0% with the 

VR1.

2) SPAN:  Apply 100% input and adjust output to 100% with 

the VR2.

3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.