10.3. A/D CONVERSION
1) 60C-x1
Analog input signal (0 – 100%) from signal conditioners is converted proportionally into digital data, provided to the Master
Unit.
INPUT (%)
115
100
FA24 (-1500)
-15
CONVERTED DATA
Hexadecimal
(Decimal)
2CEC (11500)
2710 (10000)
2) 60C-x2
Digital input signal from the Master Unit is converted proportionally into analog output signal (0 – 100%).
2710 (10000) 2CEC (11500)
DIGITAL INPUT DATA
Hexadecimal (Decimal)
-15
FA24 (-1500)
115
100
OUTPUT (%)
3) OUTPUT IN AN ABNORMALITY
When an abnormality such like CPU error, STOP, time-out occurs at the PLC, the output signal of the 60C is maintained as
HOLD (no clearing output signal, keeping the value just before the abnormality).
When the PLC recovers to normal operation and the 60C receives new data, the output restarts changing.