47LM
P. / 6
EM-9504-B Rev.1
SETTING PROCEDURE
■
GENERAL SETTING FLOWCHART
*
1. Optional settings for parameters in a broken-line section.
Alarm Setting Mode is locked with no-alarm-output type.
POWER ON
*
1
■
INITIAL SETTING FLOWCHART
Initial Setting Complete
Measuring Started
Hold down Scale/ button for 3 seconds or more to move on to Scaling Setting Mode.
Hold down Alarm/ button for 3 seconds or more to move on to Alarm Setting Mode.
Go through the alarm settings.
Hold down Alarm/ + Scale/ buttons at once for 3 seconds or more
to move on to Advanced Setting Mode. Go through the advanced settings.
Hold down Alarm/ button or Scale/ button for 1 second or more
to go back to Measuring Mode.
If necessary, hold down Max/Min Alarm/ buttons at once
for a preset time duration to enter Lockout Setting Mode.
Go through the lockout settings.
POWER ON
Measuring Mode
Hold down Alarm/ or Scale/ button
for
≥
1 second
Hold down Scale/ button
for
≥
3 seconds
Measuring
Measuring stopped
*
3
Mode transition
*
1. Preset time can be specified with “Transition Time to Lockout Setting Mode” in Advanced Setting Mode.
*
2. Alarm Setting Mode is locked with no-alarm-output type.
*
3. The last measured values or status are held for DC and alarm outputs while the measuring is stopped.
(Except the analog output adjustments during the loop test and the scaling setting)
Scaling Setting Mode
Alarm Setting Mode
Advanced Setting Mode
Hold down Alarm/ or Scale/
button for
≥
1 second
Hold down Alarm/ or Scale/ button
for
≥
1 second
Hold down Max/Min + Alarm/ buttons at once
for a preset time duration
*
1
Hold down Alarm/ + Scale/ buttons at once
for
≥
3 seconds
Lockout Setting Mode
Hold down Alarm/ or Scale/ button
for
≥
1 second
Hold down Alarm/ button
for
≥
3 seconds
*
2
Loop Test Output Mode
Hold down Alarm/ or Scale/ button
for
≥
1 second
Hold down Alarm/ + Scale/ + Shift buttons at once
for
≥
5 seconds